Comet H0430 Specifications |
Technical parameters |
Value |
Output |
RS485 |
Measured Value |
Temperature |
Construction Type |
Ambient Air |
Design |
Industrial |
Temperature Measuring Range |
-30 to 80 °C |
Relay Output |
Yes |
Two-State Input |
Yes |
Lcd Display |
Yes |
PoE |
No |
Maximum switching voltage, current, power of relay output |
50V, 2A, 60VA |
Audible alarm |
from built-in beeper - switchable |
Accuracy of temperature output |
±0.4°C |
Available temperature units |
degrees Celsius, Fahrenheit |
Signal for binary inputs |
dry contact, open collector or two-state voltage signal. Inputs are not galvanically isolated. |
Minimum pulse length at binary input |
500 ms |
Voltage at open contact |
3.3 V |
Low voltage level |
0 to +0.5 V |
High voltage level |
+3.0 to +30V |
Temperature operating range |
-30 to +80°C |
Temperature operating range of LCD display |
readable to operating temperature +70°C, it is recommended to switch OFF the LCD over +70°C |
Communication protocol |
ModBus RTU and Advantech ADAM compatible protocol |
Communication speed |
110 to 115200 Bd |
IP protection |
IP65 |
Power |
9-30Vdc, power consumption approximately 1W |
Dimensions |
136 x 191 x 45 mm (W x H x D), stem length 53 mm |
Weight |
approximately 350g |
Warranty |
3 years |