Measurements:
Temperature
Relative humidity
CO2 (optional)
Combustibles (optional)
VOCs (optional)
CO (optional)
O2 (optional)
NH3 (optional)
NO (optional)
NO2 (optional)
HCHO (optional)
SO2 (optional)
H2S (optional)
|
23 to 131 °F (-5 to 55 °C)
0 to 99.9% (non-condensing)
0 to 5000 ppm; 0 to 10,000 ppm; 0 to 5%; 0 to 20%; 0 to 100%
0 to 5% volume CH4
0 to 50 ppm; 0 to 300 ppm
0 to 50 ppm
0 to 25%
0 to 50 ppm
0 to 100 ppm
0 to 5 ppm
0 to 10 ppm
0 to 20 ppm
0 to 50 ppm
|
Display
|
LCD with backlight, shows all readings simultaneously
|
Power
|
3x AA batteries or via included wall adapter
|
Run Time
|
12 to 14 hours, depending on sensors installed and battery type (continuous using wall adapter)
|
Sampling Method
|
Diffusion or aspirated (pump)
|
Memory
|
> 1 million records (with optional SD card)
|
Size (H x W x D)
|
7.8 x 3.1 x 3.9 in. (19.8 x 7.9 x 9.9 cm)
|
Weight
|
20 oz. (567 g)
|
Operating Conditions
|
41 to 122 °F (5 to 50 °C), 0 to 99% RH (non-condensing), 1 ATM ± 10%
|
Warm-up Time
|
30 seconds
|
Approvals
|
CE mark
|
Warranty
|
Instrument: 2 years
Sensors: 1 year
|