Operation Frequency |
During R measurement, operator should select the following test frequencies: 270 Hz ± 1 Hz or 1470 Hz ± 1 Hz |
Voltmeter |
In the voltmeter function, the equipment operates as a CA VoLTMETER conventional voltmeter, making it possible to measure voltages generated by parasitic currents. |
Measurement Ranges |
Resistance: 0 - 20 kΩ (autoranging)
Resistivity: 0 - 50 kΩm (autoranging)
Voltage: 0 - 60 V |
Accuracy |
Resistance and Resistivity measurements:
R ≤ 2 kΩ: ± (2% of the measured value ± 2 digits)
R > 2 kΩ: ± (5% of the measured value ± 2 digits)
Voltage measurement: ± (3% of the measured value ± 2 digits) |
Reading Resolution |
0.01 Ω in the resistance measurement
0.01 Ωm in the resistivity measurement
0.1 V in the voltage measurement |
Output Current |
The short-circuit current is limited to less than 3.5 mA RMS (according to IEC 61557-5 - 4.5) |
Immunity to Spurious Voltage Interference |
During the R measurement, it allows the presence of spurious voltage up to 7 V. |
Earth Resistance of Auxiliary Rods |
In the R measurement it allows Raux up to 50 kΩ with error <30%. |
Battery Status Chec |
The battery charge status is verified under normal use conditions. |