Specification:
Input data
Input signal 0/4...20 mA
Voltage drop at input 3.5 V + IOUT × RO
Output data
Output signal 0/4...20 mA
Load resistance RO 0...500
Galvanic separation transformer-based
Strength test parameters 1.5 kV, 50 Hz, 1 min
Dynamic characteristics
Transmission band 5 Hz (3 dB)
Conversion errors
Accuracy ±0.16%
When converting a 0...20 mA signal to 0...20 mA in the range below 1% of signal, the error increases to ±0.5%.
Effect of temperature fluctuations 0.1% / 10°C
Effect of load resistance fluctuations 0.1% / 100
Conditions of normal use
Ambient temperature 5...60°C
Relative humidity 30...80%
Casing
Type ME 12.5 (PHOENIX)
Ingress protection rating IP 20
Weight 0.1 kg