Bộ điều khiển nhiệt độ TASHIKA SRS1, SRS3, SRS4, SRS5


Display
Digital display: Measured value (PV): 7-segment red LED, 4 digits
Target set value (SV): 7-segment green LED, 4 digits
SRS1 PV height of character: Approx. 13.8mm/ SV height of character: Approx. 10.65mm
SRS3 PV height of character: Approx. 21.8mm/ SV height of character: Approx. 14.6mm
SRS4 PV height of character: Approx. 13.8mm/ SV height of character: Approx. 10.65mm
SRS5 PV height of character: Approx. 22.0mm/ SV height of character: Approx. 10.6mm
Action display: LED lamp display: Color
Auto tuning (AT): Lights during standby (flashes during execution): Green
Action display (RUN): Lights during fixed value control operation (FIX): Green
Flashes during program RUN program control operation (RUN): Green
Control output (OUT): Lights during contact or SSR drive voltage output: Green
For voltage/current output, lights when output is 100%
In other cases, flashes at intervals of 0.5 sec. (multiples of 0.5 sec.).
Manual control output (MAN): Flashes during manual output is ON: Green
Event (EV1, EV2): Lights during event output: Orange
Display resolution: Differs according to input range (0.001, 0.01, 0.1, 1)
Display accuracy: TC: ±(0.3%FS + 1 digit + 2 °C)
Pt: ±(0.3%FS + 1 digit + 0.1 °C)
mV: ±(0.3%FS + 1 digit)
V: ±(0.3%FS + 1 digit)
Display accuracy maintaining
range: 23 °C±5 °C
Measured value display range: -10–110% of measuring range (not below -273.15 °C : T/C input)
-10–110% of measuring range (not below -240 °C : RTD input)
Display cycle: 500 ms (0.5 seconds)
nSetting
Setting method: By operating 4 front panel keys ( , , , )
Target value setting range: Same as measuring range (within setting limiter)
Setting limiter: Individual setting for higher & lower limits are possible
Within measuring range (lower limit value < higher limit val