- The current relay STW20V monitors the current in up to 3 lines with current transformers STWA 1 (AND circuit). If there is a current in all 3 monitored lines, the relay (2 change-over contacts) picks up. If there is no current in at least one of the lines, the relay releases.
- The relay works in closed circuit current. When voltage is applied to the STW, the relay signals an alarm until the it has picked up. This can be avoided if the device is constantly alive and monitoring is started by closing a contact at the Enable input. With a bridge at the Enable input, monitoring is automatically started when voltage is applied.
+ 3 inputs (transformer STWA1)
+ 3 x current-sensor S1 (powersupply required)
+ AND-evaluation
+ output relay 2 CO
+ switching point app. AC 1 A
+ Enable-input
+ storage of alarms or Auto-Reset
+ LEDs power on and alarm
+ housing V4 for mounting on DIN-rail or wall-mount
Thông số kỹ thuật
- Power supply Us.......AC/DC 24 - 240 V, < 3 W, < 5 VA,(AC 20 - 264 V, DC 20,4 - 297 V) AND-evaluation
- Function.......AND-evaluation
- Transformer input.......1 or 3, type STWA 1
- Overload cap. continious/max.10s.......100A / 300 A
- Switching point on.......≤ AC 1 A
- Switching point off.......≥ AC 0,3 A
- Switch-off delay.......approx. 0,3 s.
- Switch-on delay.......approx. 0,3 s.
- Overload capacity.......with STWA 1 unlimited
- Output relay.......2 CO
- Type of contact.......type 2 see general technical informations
- Testing conditions.......see general technical informations
- rated ambient temperature range.......-20°C…+55°C
- Dimensions H x B x T.......Design V 4: 90 x 70 x 58 mm
- Protection housing / terminals.......IP 30 / IP 20
- Weight.......approx. 240 g