Máy đo tỷ số máy biến áp Phenix PATTR-3D
Manufacturer Specs
General Speicifications |
Ratio range |
0.6 to 50000 |
Ratio accuracy |
0.03% from 0.8 to 1000:1 at 275 V
0.05% from 0.6 to 1000:1 with 8 V, 40 V & 100 V
0.1% from 1000 to 5000:1
0.2% from 5000 to 10000:1
0.3% from 10000 to 50000:1 |
Test voltages |
8 V, 40 V, 100 V, 275 V |
Power input |
100 V to 265 V, 45-65 Hz. MUST BE SPECIFIED AT TIME OF ORDER |
Phase angle range |
±180 degrees |
Phase angle accuracy |
±0.05 degree |
Phase angle resolution |
±0.1 degree |
Magnetizing current
range |
Up to 2 A |
Magnetizing current
accuracy |
±1% of reading + 1 digit |
Measuring time |
5 to 10 seconds |
Data Storage |
> 10,000 test files |
Display |
Backlight 6.5" LCD, 640x480, Ultra high brightness |
Data displayed |
• Vector group, phase, tap position, ratio, ratio deviation, phase angle displacement, excitation current, pass-fail results
• Up to 3 test files can be loaded simultaneously for comparison
• Graphical and tabulated representation of test results |
Interface |
USB (USB memory drive), Ethernet (remote control) |
Tested for |
EMI, Safety |
Dimensions/Weight (approx.) |
55 lbs (25 kgs)
20” (508 mm) L x 16” (406 mm) W x 9” (229 mm) H |
Shipping Size
(approx.) |
60 lbs (27 kgs)
24” (610 mm) L x 21” (533 mm) W x 15” (381 mm) H |
|