| Control |
| |
8-step switch for air volume and temperature |
|
| |
Air volume Stage 0 [m³/h] |
6,000 |
| |
Temperature increase Stage 0 [°C] |
|
| |
Air volume Stage 1 [m³/h] |
6,000 |
| |
Temperature increase Stage 1 [°C] |
15 |
| |
Air volume Stage 2 [m³/h] |
6,000 |
| |
Temperature increase Stage 2 [°C] |
25 |
| |
Air volume Stage 3 [m³/h] |
6,000 |
| |
Temperature increase Stage 3 [°C] |
40 |
| |
Air volume Stage 4 [m³/h] |
4,000 |
| |
Temperature increase Stage 4 [°C] |
|
| |
Air volume Stage 5 [m³/h] |
4,000 |
| |
Temperature increase Stage 5 [°C] |
20 |
| |
Air volume Stage 6 [m³/h] |
4,000 |
| |
Temperature increase Stage 6 [°C] |
40 |
| |
Air volume Stage 7 [m³/h] |
4,000 |
| |
Temperature increase Stage 7 [°C] |
60 |
| Electrical values |
| |
Mains connection |
400 V/50 - 60 Hz |
| |
Nominal current consumption [A] |
123 |
| |
Power input [kW] |
84 |
| |
Recommended fusing [A] |
125 |
| Electric connection |
| |
Connection plug |
CEE 125 A, 5-pin |
| |
Termination |
|
| |
Minimum cable cross-section [mm²] |
50 |
| Safety feature |
| |
Overheating protection |
Available |
| Sound values |
| |
Distance 3 m [dB(A)] |
76 |
| Hose connector |
| |
Diameter [mm] |
450 |
| |
Max. hose length [m] |
100 |
| Dimensions |
| |
Length (packaging excluded) [mm] |
1,625 |
| |
Width (packaging excluded) [mm] |
800 |
| |
Height (packaging excluded) [mm] |
1,270 |
| Weight |
| |
(packaging excluded) [kg] |
245 |
|