- Universal Measuring-Transducers MU1001K can measure DC-signals up to 300 V. Pre-set measuring-ranges can be selected by the user. More measuring-ranges (zero and full scale) can be easily scaled. The output-signals DC 0/2-10 V and 0/4-20 mA are insulated from measuring-input and supply-voltage.
- Output signal 0-20mA and 0-10V or 4-20mA and 2-10V
- Rated Supply Voltage AC/DC 24-240V
- Insulation between inputs, outputs and supply voltage
- Standard ranges adjustable, universally scalable input ranges
- Inputs :
+ DC -300 … 300 mV (preset values: 0…60 / 0…150 / 0…300 / -60…60 / -150…150 / -300…300 mV)
+ DC -10 … 10 V (preset values: 0…10 / 2…10 / -10…10 V)
+ DC 0 … 300 V (preset values: 0…20 / 0…50 / 0…100 / 0…200 / 0…300 V)
Thông số kỹ thuật
- Rated supply voltage Us.......AC/DC 24 – 240 V 0/50…400 Hz < 3 W < 8 VA
- Tolerance.......DC 20,4 - 297 V ; AC 20 - 264 V
- Dimension (H x W x D).......75 x 22,5 x 110 mm
- Line connection solid wire.......each 1 x 0,5…2,5 mm2
- Stranded wire with insulated ferrules.......each 1 x 0,14…1,5 mm2
- Torque.......0.5 Nm (3,6 lb.in)
- Protection class housing.......IP 40
- Protection class terminals.......IP 20
- Mounting.......Snap mounting on 35 mm standard rail EN 60 715 or M4 screws
- Weight.......app. 100 g