- Features
-
- Portable, Simple setup and easy handing
- CANopen connectivity
- 4TPDO, Dynamic PDO-Linking and Mapping, SDO server
- Life guarding, Node guarding, Heartbeat Producer
- Low-cost IO modules addition to existing PLC system
- IO modules used with the third party software via CANopen protocol.
- Interface with field devices to provide real-time data for SCADA / PLC / HMI
- LEDs on every modules for digital IO status, communication and power supply
- Different types of IO Modules AI, AO, DI, DO, RTD, Thermocouples are available
- Direct reading of temperature without scaling by using RTD and Thermocouple Modules
- Specification
-
|
|
|
Power Supply |
Logic Supply Voltage |
12 -24 Vdc |
Logic Supply Current |
86mA @ 12V / 45mA @ 24V |
RTD Inputs |
Input Points |
4 |
RTD Configuration |
2, 3 or 4 Wire |
Resolution |
0.1°C |
Drift |
50ppm/°C Typ. |
Line resistance effect |
< 0.1°C balanced |
Max. line resistance |
50ohms |
Input update rate |
10ms - 60ms (selectable) |
Isolation |
1500Vrms between field and logic |
RTD Type |
Number |
Type |
Range |
Accuracy |
1 |
PT100 |
-200 to 850°C |
0.3°CIEC 751:1983 |
2 |
Ni120; |
-80 to 320°C |
0.3°C |
3 |
PT1000 |
-200 to 850°C |
0.3°C |
4 |
Ni1000-DIN |
-200 to 850°C |
0.3°C |
5 |
Ni1000-Landys&Gyr |
-200 to 850°C |
0.3°C |
6 |
Ohms |
0 - 400 ohms |
|
7 |
Ohms |
0-4000ohms |
|
CANopen Data |
NMT. |
Slave |
Error Control |
Node Guarding / Consumer Heartbeat |
Node ID |
DIP switch or software |
Number of PDO |
4 Tx |
PDO Modes |
Event Controlled Asynchronous, Event Timer Asynchronous, Sync - Acyclic, Sync – Cyclic. |
PDO Mapping |
Variable |
PDO Linking |
Supported |
Number of SDO |
1 Server |
Error Message |
Yes |
Temperature |
Operating Temperature. |
-20°C to + 70°C |
Storage Temperature |
-40°C to + 85°C |
Connectors |
Logic Power and Comms. |
5 way connector that clips onto DIN rail |
Inputs |