A. GENERAL
Differential Level Transmitter to consist of two non-contacting ultrasonic sensors, connecting cable, and a remote enclosure with indicating, transmitting and controlling electronics.
Measurement accuracy shall be ±0.25% of Range or 2 mm (0.08"), whichever is greater, and shall be automatically temperature compensated.
Sensor cable length shall be as required by installation, not to exceed 500 ft (152 m).
System shall have no moving parts and shall not contact the material being measured.
B. SENSING ELEMENT
Ultrasonic sensors shall be constructed of PVC.
Sensors shall have a minimum deadband or blanking of 8" (203.2 mm) and a maximum range of 15 ft. (4.57 m), and have an operating frequency of 92 kHz with an ultrasonic beam angle of 8 Degrees.
Sensors shall withstand accidental submersion to 20 psi (1.4 bar).
Sensor operating temperature shall be from -40°F to 150°F (-40°C to 65°C).
Sensors shall include integral temperature sensor. Temperature sensors requiring separate mounting and wire runs shall not be accepted.
C. SENSOR CONNECTING CABLE
Provide RG62AU coaxial cable 25' (7.6m) continuous length, with waterproof, potted bond to the Sensor head.
Extended sensor cable shall be RG62AU coaxial to a maximum of 500' (152m) for each sensor. Cable shall be spliced with screw terminal connections in manufacturer's recommended steel NEMA4 Junction Box.
Level and temperature signals shall be conducted on one single coaxial cable. Separate or multiple-conductor cables shall not be accepted.
Sensor cable shall be installed in grounded metal conduit.
D. TRANSMITTER
The transmitter shall include a built-in 5-Key calibration system with operator selection of parameters through visual prompts from a Menu calibration system. Systems requiring calibration by Parameter codes or external calibrators shall not be accepted..
Calibration data shall be permanently stored through power interruptions without requirement of a back-up battery.
Field calibration shall allow selection and automatic conversion of measurement units, measurement span and control relays.
The transmitter shall provide for field calibration in user-selected Level, Range and/or Open Channel Flow modes. Operation mode shall be user-selectable for differential level, differential level plus open channel flow, level/volume in two tanks or submerged flow alarm in Parshall flumes.
Transmitter shall permit field programmable damping to smooth output in turbulent level conditions and to disregard false signals from waves and spurious echoes.
Transmitter electronics operating temperature shall be from -5° to 140°F (-20° to 60°C).
Transmitter shall have three isolated 4-20mA outputs each with 1000 ohm maximum load. Outputs shall allow field programmable offsets of 4mA and 20mA for level, differential level and open channel flow.
Provide 2 control relay dry contacts rated 5 ampere SPDT. Relays shall be programmable for level alarm, differential level control, temperature alarm, pump control, pump alternation, flow totalizer pulse and/or echo loss alarm.
Provide a white, backlit matrix LCD display indicating level, differential level, flow rate, totalizer and relay states in user-selected engineering units.
Transmitter shall be housed in a wall-mount, watertight NEMA4X (IP 66) enclosure with hinged, clear cover. Mounting hardware shall be included.
Transmitter LCD display shall be visible without opening cover.
Transmitter electronics shall include automatic high voltage bleeds for nearby lightning strikes.
Electronics shall be modular and field replaceable by means of plug-in circuit boards. The instrument shall detect and load software menus automatically for field-installed options.
The transmitter shall be powered by 100-240VAC 50/60Hz requiring less than 3 Watts.