Line Voltage: |
5 kV to 138 kV
|
Conductor Range: |
6 mm (0.25”) up to 32:mm (1.3”)
|
Sample Rate Current: |
600 Hz, Voltage 600 Hz
|
Accuracy: |
Current: 2% of reading ± 1A
Load recording range: 1A – 25kA
Current sensor fault detection range: 5A -25kA
|
Ingress Protection: |
IP66
|
Measured Parameters: |
Current and power (On/Off)
|
Fault/Event Capture: |
60-Sec RMS profile (I & E-Field)
Pre-event Line Loading
Fault Current Magnitude up to 25 kA
Fault Current Waveform (200 ms)
E-Field Waveform % Change (200 ms)
|
Energy Storage/Power Source: |
Solar with battery backup
|
Communications: |
Local RF 150 ft (50 m); Cell (GSM/CDMA), Landline;
DNP3, Web Services SCADA & historian integration tools available
|
Memory: |
100 events (60 sec RMS records); 32 fault waveforms;
up to 85 days’ load profiling |