- Two-Winding Current Differential, Overcurrent, and Breaker Failure Protection
Apply two-winding dual-slope differential protection with phase, negative-sequence, residual, and neutral overcurrent elements for backup protection. Use breaker failure protection for two 3-pole breakers.
- Secure and Dependable
Provide maximum security during external faults and transformer magnetizing inrush conditions. Detect internal faults quickly, during energization or normal operating conditions, using combined harmonic-blocking and -restraint differential elements.
- Transformer Monitoring
Record and accumulate through-fault duty for use in SELogic control equations or manual monitoring. Monitor ambient, load tap-changer (LTC) tank and transformer oil temperature with optional 4–20 mA analog inputs or RTD thermal inputs to extend the life of your transformers.
- Operator Control
Use four programmable front-panel pushbuttons, each with two programmable LEDs, for a wide variety of applications, including easy trip-and-close control and status indications for a breaker. Implement local and remote operator control schemes with 32 local and 32 remote control bits.
- Metering and Reporting
Eliminate separately mounted metering devices with built-in metering functions. Analyze Sequential Events Recorder (SER) reports and oscillographic event reports for rapid commissioning, testing, and post-fault diagnostics. The unsolicited SER protocol allows station-wide collection of binary SER messages. SEL-787 metered quantities include harmonics, power, frequency, and energy; phase voltages and currents; neutral currents; sequence voltages and currents; and maximum/minimum logging of selected quantities.
- Rugged Design
Trust the industry’s widest ambient operating temperature range, –40° to +85°C (–40° to +185°F). The SEL-787 withstands vibration, electrical surges, fast transients, and extreme temperatures, meeting stringent industry standards. The printed circuit boards are conformal-coated to provide an additional barrier to airborne contaminants, such as hydrogen sulfide, chlorine, salt, and moisture.