- Measuring transducers MU2000K can measure DC- an AC-voltages up to 600 V and DC- and AC-currents 0-1/5 A.
- Preset measuring ranges can be selected. More measuring ranges (zero and full-scale) can be easily scaled. The output signals DC 0/2-10 V and 0/4-20 mA are insulated from measuring input and supply voltage. With its universal supply voltage AC/DC 24-240 V the measuring transducer can be connected to all common supply voltages.
- The MU2000K e.g. is suitable for measuring DC voltages and charging currents at batteries or for measuring AC voltages and currents in plants for own generation of energy.
- Output signal 0-20mA and 0-10V or 4-20mA and 2-10V
- Rated Supply Voltage AC/DC 24-240V
- Insulation between inputs, outputs and supply voltage
Thông số kỹ thuật
- Rated supply voltage Us.......AC/DC 24V-240 V, 0/50/60 Hz < 3 W < 8 VA; DC 20,4 - 297 V, AC 20 - 264 V
- Input voltage.......AC/DC 0-30/150/300/600 V, 80-120 V, Ri = 500 kΩ, max. 600 V, max. 300 V to GND
- Accuracy.......DC ≤ 0,2% AC ≤ 0,5% (50/60 Hz) from full scale, drift < 0,02 %K
- Input current.......AC/DC 1A, 5A, max. 7,5A/4s, 25A/1s, 30 mΩ
- Accuracy.......DC ≤ 0,2% AC ≤ 0,5% (50/60 Hz) from full scale, drift < 0,02 %K
- Measuring method / Resoulution.......RMS (AC), averaging (DC), resolution 14 Bit
- Output voltage.......DC 0/2-10 V, load min. 1 kΩ
- Accuracy.......≤ 0,3 % from full scale, drift <0,01 %/K
- Resolution.......11.6 Bit, <3,1 mV
- Output current.......DC 0/4-20 mA, load max. 500 Ω
- Accuracy.......≤ 0,3 % from full scale, drift <0,015 %/K
- Resoulution.......11,6 Bit, <6,1 mA
- Error load.......0,3 % of current x (250Ω - load) / 250Ω
- Galvanic insulation.......Supply voltage - input - output
- Measuring time / Averaging.......45 ms + 20 ms x number of averages (1/2/8/16/32 values)
- Rated ambient temperature range.......-20 °C ... +50 °C
- Housing dimensions (h x w x d).......design K, 75 x 22,5 x 115 mm
- Protection housing/terminals.......IP 40 / IP 20
- Attachment.......DIN rail 35 mm or screws M4
- Weight.......ca. 100 g