Hotline: 0984.843.683 Email: info@ttech.vn  Zalo: 0984.843.683

Diagnostic Surge Suppressor + Scope Meter EV12020IC SurgeX

Mã sản phẩm: EV12020IC
Sử dụng cho Model:
Hãng SX: SurgeX
Xuất xứ
Bảo hành
Tình trạng

Tình trạng: Còn hàng

Đặt hàng
enVision Diagnostic Surge SuppressorThe SurgeX EV12020IC enVision diagnostic surge suppressor is the ultimate troubleshooting tool for service organizations. Engineered with state-of-the-art power protection, electrical intelligence, diagnostic software, and real-time scope meter technology, the ESP's innovative cost-savings solution gives service teams the ability to identify power problems and eliminate unwarranted costs that can impact the profitability of your service department.

Liên Hệ Hỗ Trợ

    • SĐT: 0984 843 683

    • Mail: info@ttech.vn

      • Zalo: 0984.843.683

Thông tin sản phẩm

Features

EV12020IC Diagnostic Surge Suppressor + Scope Meter, 20 amps at 120 volts.
Measures neutral to ground voltage, crest factor, power factor, and line frequency metrics
20 Amps at 120 Volts load rating
Integrated scope meter diagnostic capabilities
Lowers service costs, ensures fault-less installs, and improves customer uptime
Identify preexisting power conditions, analyze real-time power anomalies, and generate electrical performance reports.
Internal battery to provide accurate data and time stamps, even during power outages
Built-in LCD screen provides easy access to recorded events, parameters and settings
Protects connected equipment from power disturbances
Power over Ethernet protection
Remote IP capable (sold separately)
Lifetime product and connected equipment protection warranty


Model: EV12020IC Specifications
Load Rating 20 Amps at 120 Volts
Voltage Protection Rating (VPR) 330V All Modes
Attenuation Normal Mode:> 30 dB 80kHz – 50MHz
Common Mode: > 30 dB 70kHz – 50MHz
Power Requirement (no load) 4 Watts
Under-Voltage Shutdown Adjustable from 0 V to 110 V. Default 80 V.
Under-Voltage Record Adjustable from 0 V to 110 V. Default 100 V.
Under-Voltage Restore Adjustable from 80 V to 110 V. Default 105V.
Over-Voltage Shutdown Adjustable from 130 V to 160 V. Default 150 V.
Over-Voltage Record Adjustable from 130 V to 160 V. Default 145 V.
Over-Voltage Restore Adjustable from 130 V to 160 V. Default 140 V.
Internal Memory Capacity 512 Power Quality Events with Timestamp
138 Day Electrical Parameter History at 30 minute intervals
Timestamp Accuracy ± 1% Typical Product Accuracy
Measurement Accuracy ± 2% Typical product accuracy
Response Time Over-Voltage: 90 ms
Under-Voltage: 200 ms
Power Outage Event Definition AC Voltage has dropped below 20V
Surge Event Definition Filter has been exposed to a transient voltage in one of the 3 possible modes (between Live and Neutral, between Live and Ground, between Neutral and Ground) with a peak amplitude of 500V* or higher and a frequency of 20 kHz or higher. *500V surge voltage amplitude applies to IEEE C62.41
Category B Impulse; surge voltage amplitudes necessary for detection of other surge types may vary.
Modem/Fax Protection Single telephone line surge suppression
Ethernet Protection CAT6 network surge protection
Dimensions 6.125" W x 8.375" D x 2" H
Weight 2.25 lbs
Temperature Range 5C to 40C
Humidity Range 5% to 95% R.H. Non-condensing
Agency Listings ETL Certified to UL 1449 3rd Edition
Warranty Limited lifetime product warranty and limited lifetime connected protection warranty.