| Power supply voltage |
100–240 V AC, 50/60 Hz |
| Power consumption |
≤ 5 VA (at 100 V) or ≤ 6 VA (at 220 V) |
| Input |
RTD (Pt100), thermocouples (9 types) |
| Indication accuracy |
(±0.5% of indicated value or 1°C, whichever is larger) ±1 digit ±1°C |
| Sampling rate |
0.2 s |
| SV/PV correction |
Provided |
| Control |
ON/OFF control, PID control (with auto-tuning), Fuzzy control |
| Control output |
Relay contact output or SSR/SSC driving output |
| Alarm output |
1 or 2 (option) |
| Alarm type |
absolute value, deviation value, zone, high, low, hold, alarm latch, excitation/non-excitation |
| Burnout |
If burnout occurs, the output goes to high limit or low limit. |
| Display |
7-segment 4-digit LED
Process value and set value |
| Parameter loader software |
- Allows parameter setting, editing, and saving
- No need for power supply for PXE
- You cannot control temperature via the software
|
| Enclosure |
IP66, NEMA-4X equivalent (when mounted on panel), with front waterproof packing |
| Dimensions and weight |
48 (W) × 48 (H) × 63.5 (D) mm, approx. 100 g |
| Mounting |
Panel mount (mounting fixture provided) |
| Terminal |
M3 screw terminal |
| Ambient temperature |
-10°C to +50℃ |
| Approval |
CE marking, RoHS |