| General specifications |
Mounting method |
Panel mount |
| Dimensions |
300 (W) × 300 (H) × 221 (D) mm |
| Power supply voltage |
100–240 V AC, 50/60 Hz |
| Power consumption |
Approx. 80 VA (at 240 V AC) |
| Terminal |
M3 screw terminal (Power terminal is M4 screw) |
| Input section |
Number of inputs |
9, 18, 27, or 36 (as specified by order) |
| Measurement cycle |
9 or 18 inputs: 100 ms
27 or 36 inputs: 200 ms |
| Input signal |
Thermocouple (type B, R, S, K, E, J, T, N, W, L, U, or PN)
RTD (Pt100)
DC voltage (50 mV, 500 mV, or 5 V)
DC current (with shunt resister) |
| Burnout function |
Provided as standard for thermocouple or RTD input |
| Display unit |
Display |
12" TFT color LCD (800 × 600 dots) with automatic display off function |
| Life of backlight |
50,000 hours |
| Display contents |
Trend, bar graph, digital display, event summery, tag,
Historical trend, parameter, parameter setting, group, analog meter,
Scale, total data, Ethernet log |
| Recording function |
Storage medium |
CompactFlash |
| Recording capacity |
1 GB max. |
| Data saving cycle |
Links to refreshment cycle of the trend display |
| Trend data |
Average, instantaneous value, or maximum and minimum value are saved. |
| Event data |
Alarm data, message data, power on and off are saved. |
| Data format |
ASCII (readable by Excel)
Binary (not readable by Excel) |
| Storage capacity |
Approx. 1.5 years' worth at a display refresh cycle of 30 seconds (ASCII, 9 channels, 256 MB CompactFlash) |
| Memory consumption |
Displayed in bar graph
Recording stops when the memory is full. |
| Calculation function |
|
Difference between channels, F value, integration, square root extraction |
| Alarm |
Number of settings |
Up to 4 alarms for each channel |
| Alarm type |
High/low limits |
| Indication |
Alarm status is displayed on digital display when an alarm occurs.
Histories are displayed in the alarm summary.
|
| Relay contact output |
up to 20 points (option) |
| Open collector output |
16 points (option) |
| Performance |
Indication accuracy |
±(0.15% + 1 digit) of input range |
| Indication resolution |
0.1°C |
Reference junction
compensation error |
±0.5°C |
| Others |
Memory backup |
Parameter settings are saved to the internal nonvolatile memory.
The clock is backed up by a built-in lithium battery.
Trend data is stored in CompactFlash with no back-up. |
| Option |
Alarm output |
Relay output: 10 or 20 points
Open collector output: 16 points |
| Digital input |
No-voltage contact input, 16 points |
| Communication |
Ethernet |
| Accessories |
|
CD-ROM (parameter loader software, instruction manual), panel mounting bracket, noise filter for power cable |