- Type : Ultraviolet and Infrared
- Detection Range : 100ft(30m(FM), 15m(KFI)) for N-Heptane fire
- Field of View : Horizontal 90°, Vertical 90°
- Temperature Range Operating : -40℃ to +75℃
- Storage : -50℃ to +80℃
- Humidity Range : 0 to 95% relative humidity
- Explosion proof :
+ Class I Division 1 Groups B,C and D(FM)
+ Class II Division 1 Groups E,F and G(FM)
+ Class III (FM)
+ Ex db IIB+H2 T6(ATEX, KGS)
- Output
+ Relay
- Fire Alarm, Fault Alarm, Warning Alarm
- From A or B Selectable, 28vdc, 2A
+ 4-20mA
+ RS-485
- Dimensions : W134 x H117 x D120 (mm); W5.3 x H4.6 x D4.7 (inch)
- Enclosure Material : Stainless steel 316
- Shipping Weight : 3.4 kg
- Color : Metal
- Conduit Entry Size : 2 x 1/2 inch PF
- Operating Voltage : Typical DC24V (17 to 32)
- Power Consumption : 1.8W maximum at 32 vdc
- Wiring : 14AWG(2.08mm2) to 24AWG(0.205mm2) shield cable recommended.
- Electromagnetic Compatibility : EMC Protected
|