Hotline: 0984.843.683 Email: info@ttech.vn  Zalo: 0984.843.683

Coil Tester & Power Supply POB40D DV Power

Mã sản phẩm: POB40D
Sử dụng cho Model:
Hãng SX: DV Power
Xuất xứ
Bảo hành
Tình trạng

Tình trạng: Còn hàng

Đặt hàng
Coil Tester & Power Supply
Model: POB40D
Hãng: DV Power


Liên Hệ Hỗ Trợ

    • SĐT: 0984 843 683

    • Mail: info@ttech.vn

      • Zalo: 0984.843.683

Thông tin sản phẩm

Coil Tester & Power Supply POB40D is powerful, lightweight power supply device, ideal for operating and testing circuit breakers coils. It is also intended to supply spring-charging motors with the possibility to generate the inrush current of up to 40 A DC. For supplying the circuit breaker auxiliary circuits, it provides wide output DC voltage range (10 – 300 V).
POB40D has built-in capability to perform an automatic test of minimum trip-voltage (in accordance to IEC 62271-100 and ANSI C37.09 standards).
POB40D can be used as a general power supply device or a temporary battery charger. Note that it is compatible with the circuit breaker analyzers from different vendors.



Thông số kỹ thuật



Mains Power Supply
  • Connection
according to IEC/EN60320-1; UL498, CSA 22.2
  • Voltage
90 V – 264 V AC, 50/60 Hz, Single phase
  • Power consumption
4000 VA
Output data
  • Coils output DC Voltage
10 V to 300 V DC
  • Motor output DC Voltage
10 V to 250 V DC
  • Output current
max 40 A
Measurement
  • Voltage
10 V – 300 V DC
  • Current
1 A – 50 A
  • Accuracy
± (0,25% rdg + 0,25% FS)
Environment conditions
  • Operating temperature
–10oC – +55oC / 14 F – 131 F
  • Storage and transportation
–40oC – +70oC / -40 F – 158 F
  • Humidity
Maximum relative humidity 95%, non-condensing
Dimensions and Weight
  • Dimensions
205 mm x 287 mm x 410 mm
8.1 in x 11.3 in x 16.4 in
(W x H x D) without handle
  • Weight
10,60 kg / 23.4 lbs