HTX500 series are designed in order to measure with a precision in the areas of explosion hazards, and able to measure temperature and humidity under explosion hazards such as gas, steam or dust (flammable items). 
  
 
Applied Standards : 
EN60079-11:2012   EN 60079-25:2010   EN60079-0:2012+A11:2013  EN60079-26:2015 
Ex marking : 
Transmitter : Ex ia IIC T4 Ga(Tamb=-40℃ to 60℃) 
Transmitter : Ex ia IIIB T200℃ Da 
Remote sensing probe : Ex ia IIC T2-T5 Ga(Tamb=see schedule) 
Remote sensing probe : Ex ia IIIB T*** Da(Tamb=see schedule) 
Entity parameters : 
Ui = 28V, Ii = 100mA, Pi = 650mW, Ci = 5nF, Li = negligibly low 
Ambient Temperature : 
Transmitter without display : -40...+60℃ 
Transmitter with display : -20...+60℃ 
Remote sensing probe : -40...+180℃ 
 
 
Temperatures
    
        
            Measuring range 
            (Output ranges) | 
            -40…60℃ (wall mounting) | 
         
        
            | -40…180℃ (remote sensing probe) | 
         
        
            | Accuracy | 
            ±0.2℃ at +20℃ | 
         
        
            | Over temperature range | 
         
        
            | sensor | 
            Pt100 RTD (DIN EN 60751, Class A) | 
         
    
 
 
  
Humidity
    
        
            | Measuring(output) range | 
            0…100%RH | 
         
        
            | Accuracy (including non-linearity, hysteresis and repeatability) | 
         
        
            | At 15…30℃ | 
            ±2%RH (10…90%RH) | 
         
        
            | ±3%RH (<10%RH, >90%RH) | 
         
        
            Speed of response 
            (t90, at 20℃) | 
            <20sec (mesh filter) | 
         
        
            | <40sec (sintered filter) | 
         
    
 
  
Specification
    
        
            | Operating voltage | 
            Vcc min = (10+RL*0.02)Vdc, Vcc max = 28Vdc | 
         
        
            | Electrical wiring | 
            Screw Terminals 
            Wire: AWG 15-24(1.65 ~ 0.2mm²) 
            It is recommended that cable end is fitted to fork-terminal | 
         
        
            | Cable glands | 
            M16, Cable diameter: 4-8mm | 
         
        
            | Operating temperature range | 
            Transmitter without display: -40…+60℃ 
            Transmitter with display: -20…+60℃ 
            Remote sensing probe: -40…+180℃ | 
         
        
            | Storage temperature range | 
            -40…70℃ | 
         
        
            | Material of probe | 
            Stainless steel (SUS 304) | 
         
        
            | Probe cable | 
            Teflon FEP | 
         
        
            | Material of housing | 
            Stainless steel (SUS 316) | 
         
        
            | Protection classification of housing | 
            Ip65 | 
         
        
            | Size of housing | 
            181 x 97 x 53 mm | 
         
        
            | Weight of housing | 
            1.74kg (model: LCD type) | 
         
    
 
 
 
 
Analog Output Specification
    
        
            | Two analog outputs | 
            2-wire 4…20mA | 
         
        
            | Accuracy | 
            Typ. ±0.05% F.S at 20℃ | 
         
        
            | Road resistance | 
            RL ≤ (Vcc-10V) / 0.02A | 
         
    
 
 
 
                             |