- Industrial & multi-function;Duct/Remote type;Remote: 2-meter cable
- -80∼80℃(temp.);-80∼60 dp ℃(dew point);-80∼0 fp ℃(frostpoint temp.); 0∼20mA/4∼20mA/0∼1VDC/0∼5VDC/0∼10VDC
- With RS485 and MODBUS RTU communication interface that can play by program, data log, and analyze chart will be easy to monitoring. Physical parameters of outputs anfd range are programmable
- Physical parameters are such as temperature, dew point, frost point, absolute humidity(ppm/v or ppm/w)
Thông số kỹ thuật
- Mearsuring Range
+ Temperature : -40~80℃ ; Dew point : -60~60 dp ℃
- Accuracy ( at 25℃ )
+ Temperature : ±0.15℃±0.002℃ x tactual
+ dew point:± 3 dp ℃ ± ( 0.02 % F.S / ℃ )
+ Temp. influence of body (at+25℃) : 0.02%F.S./℃
- Output : 0~20mA / 4~20mA / 0~1V / 0~5V / 0~10V
- Signal Connection : 3-wire
- Load Resistance
+ current output max. 500 Ω
+ voltage output min. 10 KΩ
- output calibration ( ZERO & SPAN) : software
- Power Supply : 8~35VDC/12~30VAC
- Protection Degree : body IP : 65 ( probe : IP 20 )