- IEEE C37.118.1-2005 compatible PMU device
- Synchronized via internal GPS Satellite receiver
- Market leading synchrophasor support
- Revenue Accuracy: 0.025 %
- Power Quality: Harmonics, Flicker, Interruptions
- Phasor Measurements for Stability & Flow Analysis
- System Time & Frequency Deviation
- Internal Data/Event Logging
- Two Year Warranty to the original owner/purchaser
Thông số kỹ thuật
Range (3 Ø/1 Ø) |
0 Vrms to 69 Vrms, 120 Vrms, 240 Vrms, or 480 Vrms, selectable (phase-to-phase for 2 element; phase-to-neutral for 2½ element and 3 element)
|
Overrange |
88 Vrms, 175 Vrms, 350 Vrms, or 700 Vrms, nominal
|
Range (3 Ø/1 Ø) |
2.5 Arms, 5 Arms, 10 Arms, or 20 Arms, selectable, per element
|
Overrange |
2.9 Arms, 5.9 Arms, 11.7 Arms, or 23.5 Arms, nominal (maximum continuous input current: 20 Arms per element)
|
Range |
Product of rated voltage and current ranges and number of elements (2½ (3 Ø) and 1½ (1 Ø) element, use 3 and 1, respectively)
|
CT and PT |
Both magnitude and phase compensation, CT with 12 point nonlinear interpolation
|
Transformer |
Both iron and copper compensation
|
Range |
45 Hz to 65 Hz, for specified accuracy
|
Harmonics |
To 3 kHz
|
|