Measuring ranges: 10, 20 or 30 mm/s eff, selected via a internaldip – switch S.
Filter: Band Pass, 20 dB/Decade
Frequency Range: 10...1000 Hz
Cut-off frequencies: 10 and 1000 Hz (-10%)
Internal Control: Controlled is an interruption or a short circuit in the transducer or in the cable connections.
Fault indication: As 2-mA-Signal from the analog output (current) and as red LED indicator inside of the casing.
1 Analog output (Current): 4 to 20 mA, max. load 500 Ohm.
1 Analog output (Voltage): Unfiltered transducer signal. (Short circuit proofed and without reaction decoupled). Sensitivity = 100 mV/g