Hotline: 0984.843.683 Email: info@ttech.vn  Zalo: 0984.843.683

Thiết bị đo lưu lượng PIOX ID Flexim

Mã sản phẩm: PIOX ID
Sử dụng cho Model:
Hãng SX: Flexim
Xuất xứ
Bảo hành
Tình trạng

Tình trạng: Còn hàng

Đặt hàng

The false media fill-up of chemicals during delivery and transfer from tank trucks into storage tanks can have fatal consequences. These mix-ups lead to serious accidents again and again, especially when acids and alkalis are mixed. In order to prevent such dangerous situations, the hazardous substances committee recommends monitoring of the filling line.

Liên Hệ Hỗ Trợ

    • SĐT: 0984 843 683

    • Mail: info@ttech.vn

      • Zalo: 0984.843.683

Thông tin sản phẩm

Sonic velocity – a characteristic media property


PIOX ID determines the acoustic velocity of the medium using clamp-on ultrasonic transducers mounted on the outside of the filling lines. The acoustic velocity is a substance-specific variable and constant at a given temperature. Given the acoustic velocity’s dependence on the media temperature, this is also measured by PIOX ID.


If the acoustic velocities of two media differ, these can be identified by way of measurement. In particular, since the acoustic velocities of acids and alkalis are very different from one another, the safety function can be implemented easily and reliably due to the significant measuring effect.


A significant application of PIOX ID is the reliable detection of sodium hypochlorite. If sodium hypochlorite is in contact with an acid, a violent exothermic reaction occurs in which toxic chlorine is released. Many other chemicals carry similar risks. Chemical mix-ups can have disastrous consequences, be it explosions or the formation of dangerous substances such as nitrous gases or hydrogen chloride.


These dangers must be controlled safely. PIOX ID offers protection. The media identification system ensures that acids and caustics can never be confused.


State-of-the-art redefined


PIOX ID is a proven innovation in practice. The non-invasive media identification system was developed in collaboration with experts on safety at work. Unlike other methods such as temperature and pH measurement, the acoustic measurement technology is completely wear-free and does not require any maintenance. National rules for the handling of hazardous substances thus recommend the use of ultrasonic measurement as an appropriate technique for monitoring the filling line.


PIOX ID is factory preconfigured so that the protection function can be set up easily and reliably. The media identification system releases the filling process only if the value for the acoustic velocity measured by PIOX ID is within the range of the target value for the target medium. In all other cases, the filling process is stopped.


The selection of the target medium is made either according to the customer‘s specification at the factory or by an authorised person when the device is put into operation. In normal operation mode after commissioning, it is no longer possible to make changes to the stored parameters. The transmitter then only indicates whether the desired target medium is in the pipe, the pipe is empty, or a wrong medium is present and there is therefore a risk.