                                 Features 
 
 
● Current transformer (CT) testing in accordance with the current ratio error test of the international standard IEC 60044-1 is available. 
● Voltage transformer (VT) testing in accordance with the voltage error test of the international standard IEC 60044-2 is available. 
● The ratio error, phase displacement, test voltage, test current, and test frequency of CT/VT can be measured. 
● Units of indication, either “%” or “RCF” (Ratio Correction Factor) for the ratio error, and either “Min “(minutes) or “Crad” (centiradians) for the phase angle, are available. Thus, it is appropriate for ANSI/IEEE tests. 
● USB interface is a standard fixture. 
● Error values of standard VT/CT can be registered, and automatically compensated. 
Registration: 10 units for each VT and CT (Test point: 20 points for every unit) 
● Different-ratio testing is available by incorporating an optional CT or VT different-ratio adapter. 
● An internal burden compensation circuit realizes the internal burden of DAC-VCTT-8 as small as 0.1VA. 
                             |