The portable cable test set KPG 24kV VLF is used for testing of medium voltage cables in accordance to the standards IEC 60502-2, CENELEC HD 620 & 621, DIN VDE 0276/620 & 621 and IEEE 400.
Test is carried out with a low strain practice with VLF (very low frequency) test voltage of preferably 0.1Hz.
VLF testing enables detection of damages of insulation within shortest test time.
Thông số kỹ thuật
Technical data |
KPG 24kV VLF |
Power supply |
230 V (± 10%), 10 A, 50/60 Hz |
Output voltage |
5...24 kVrms (34 kVpeak), 0.1 Hz VLF (0.05 + 0.02Hz optional)
± 0...34 kV DC |
Voltage waveshapes |
VLF: similar sine-wave, symmetrical, with true R.M.S. measurement
DC: direct voltage, negative and positive polarity |
max. load (VLF) |
5.0 µF at 24 kVrms , 0.1 Hz (app. 20 km)*
15 µF at 24 kVrms , 0.02 Hz (app. 60 km)*
6.8 µF at 18 kVrms , 0.1 Hz (app. 27 km)*
*at a cable capacitance of 0.25 μF/km
|
Overcurrent trip (DC) |
10 mA |
Discharge |
integrated automatic discharge device, max 9000 J
|
Voltage measuring range |
-40 ... 0 ... 40 kV, accuracy 1%
|
Current measuring ranges |
± 0 ... 100 µA / 1 mA / 10 mA |
Operating temperature |
-20 ... +45°C |
Duty |
Continuous operation |
PC interface |
USB flash drive |
Construction |
in two parts, Operation unit and High Voltage unit |
Weight
Operation unit
HV unit |
17 kg
38 kg |
Dimensions (W x H x D)
Operation unit
HV unit |
37 x 34 x 20 cm
40 x 41 x 24 cm |
>>> KPG 36kV VLF giá tốt
|