Hotline: 0984.843.683 Email: info@ttech.vn  Zalo: 0984.843.683

Vertical Bushing 7022/4000 Measurements International

Mã sản phẩm: 7022/4000
Sử dụng cho Model:
Hãng SX: Measurements International
Xuất xứ
Bảo hành
Tình trạng

Tình trạng: Còn hàng

Đặt hàng
Vertical Bushing
Model: 7022/6000 series
Hãng: Measurements International

Liên Hệ Hỗ Trợ

    • SĐT: 0984 843 683

    • Mail: info@ttech.vn

      • Zalo: 0984.843.683

Thông tin sản phẩm

The Model 7022/4000  of High Voltage Current Transformers was designed for the current input to MI’s ALMS 4200 Loss Measurement Systems. For voltages below loo kV see the Model 7021U/4000. This design meets the requirements of both CEIJIEC 44-1 and IEEE STD C57.12.00-2000. The bushing is filled to approximately 65 PSI absolute of SF6 and is fitted with a pressure indicator or with an optional pressure transducer with a 4-20 mA output for continuous monitoring. Connections to the primary winding of the current transformer are made via a copper bar, machined at both ends. Utilizing passive two stage compensated technology, errors of less than lo ppm can be achieved at high voltages.

The main advantage of a two stage compensated CT is that the effective burden is O when feeding into another compensated CT such as the current input on the Model 2010A Wattmeter. As a result, the errors of the CT are effectively reduced to zero in both magnitude and phase. Lead length becomes unimportant and there is no further concern for any additional active components. If the 7022/4000 is connected to a wattmcter that has only a two wire input, the secondary and auxiliary leads must be connected together as close as possible to the input of the wattmeter. Typical errors for burdens at 1 are less than 100

ppm. For more accurate data on errors related to burdens above 100 m2 contact the factory.

Thông số kỹ thuật

gia-7022-4000-o-ha-noi

>>> 7021/4000 mua ở đâu là tốt?

Bình luận