100 kV AC voltage booster test equipment ITS-A100050AZ Tokyo Seiden

Mã sản phẩm: ITS-A100050AZ
Sử dụng cho Model:
Hãng SX: Tokyo Seiden
Xuất xứ
Bảo hành
Tình trạng

Tình trạng: Còn hàng

Đặt hàng

This is an automatic / manual buck-boost type AC insulation withstanding voltage tester with a maximum voltage of 100 kV and consists of two parts, the operation part and the transformer part. Also, it is equipped with input for external safety switch.

Liên Hệ Hỗ Trợ

    • SĐT: 0984 843 683

    • Mail: info@ttech.vn

      • Zalo: 0984.843.683

Thông tin sản phẩm

Electrical specifications
I / O characteristics are specified when input voltage AC 200 V 50 Hz.
input Number of phases Single-phase
frequency 50/60 Hz
Power consumption About 5.5 kW or less (at full load)
About 0.4 kW or less (no load)
Rated voltage AC 200 V ± 10%
output Rated time Half an hour
capacity 5 kVA
Voltage AC 0 to 100 kV
ground One end ground
voltmeter DPM AC 0 to 100.0 kV ± 1.5% FS 
Sample hold / peak hold 
upper limit voltage setting 
Available setting range AC 0 to 110.0 kV ± 5% FS
ammeter DPM AC 0 to 75.0 mA ± 1.5% FS
Boost method [Automatic] / [Manual] [Automatic] Automatically boost up to the upper limit set voltage after START, Automatic buck at the time of arrival Automatic buck 
at the time of overcurrent After voltage hold, output OFF OFF Automatic buck
[Manual] After step START, pushbutton operation Manual buck-boost Overvoltage 
hold after voltage hold, output OFF
Boost speed 500 - 750 - 1000 V / sec ± 10% (Can be finely adjusted about ± 5%)
Step down speed About 5 kV / sec (± 20%) (Fixed fine adjustment is impossible)
Cutoff current 10 - 20 - 30 - 40 - 50 mA ± 5%
External input / output "DoorSW" input Terminal number (TB 2 - 9, 10) 
Output ON with short circuit possible
Voltmeter terminal Terminal number (TB 2 - 1, 2) 
External voltmeter (0 - 100 kV / 0 - 100 V)
Ammeter terminal Terminal number (TB 2 - 3, 4) 
Not used Short circuit 
(factory short circuit)
 
General specification
Model name ITS-A100050AZ
External dimensions Operation part Approx. W 520 × D 400 × H 621 (mm)
About transformer part W 500 x D 780 x H 1710 (mm)
mass Operating part Approximately 52 kg
Transformer section Approximately 400 kg or less
Paint color Operation unit Case Munsell 5Y7 / 1 Gs50 (half gloss)
Panel Munsell N - 9 Gs 50 (half gloss)
Transformer section Munsell 5Y7 / 1 Gs50 (half gloss)
Withstand voltage Input - case AC 1500 V / min
Insulation resistance Input-case DC 500 V 20 MΩ or more
environment Installation location Indoor (no corrosive / flammable gas)
Operating temperature · humidity 0 to 40 ° C · 0 to 80% (with no condensation)
Storage temperature · humidity -10 to 50 ° C · 0 to 80% (with no condensation)