| Withstanding Voltage | 
            AC 3700V, 1 minute (between CT core and CT handle) | 
        
        
            | Insulation Resistance | 
            More than 100MΩ (between CT core and CT handle) | 
        
        
            | Storage Temperature | 
            -10℃~60℃, < 80% (without condensation) | 
        
        
            | Size and Weight | 
            Measuring CT:90.5(W)×165(H)×38(D)mm, approx.460g 
            Injection CT:90.5(W)×165(H)×38(D)mm, approx.440g 
            Main unit:190(W)×140(H)×42 (D)mm, approx.800g | 
        
        
            | Operating Temperature | 
            0℃~40℃, < 85%RH ( without condensation) | 
        
        
            | Power supply | 
            Ni-Cad battery (1.2V × 5) | 
        
        
            | Power consumption | 
            Approx. 380mA(Earth resistance measurement) | 
        
        
            | Safety standard | 
            IEC 61010-1, IEC61010-2-032 
            Installation CAT II 600V or CATⅢ 300V | 
        
        
            | Limitation of circuit voltage | 
            Less than 500V | 
        
        
            | Accessories | 
            Measuring CT:1 
            Injection CT:1 
            Battery charger:1 
            Carrying case:1 
            Subsidiary lead wire:1 
            Instruction manual:1 | 
        
        
            | Display | 
            LCD, 16 letters/characters × 2 lines 
            with contrast adjuster | 
        
        
            | Measuring function | 
            Earth Resistance, AC Current (Load and Leakage) | 
        
        
            | A/D Conversion | 
            Dual slope integration mode | 
        
        
            | Over range indication | 
            "OVER" on LCD | 
        
        
            | Data hold indication | 
            "DH" mark on LCD | 
        
        
            | Low battery indication | 
            "B" mark on LCD | 
        
        
            | Battery life | 
            Approx.400 times measurements under full charged condition (Subject to the times of charging and discharging) | 
        
        
            | Sampling | 
            Approx. 2 times/sec. for AC current | 
        
        
            | Auto power off function | 
            Approx. 5 minutes after power on | 
        
        
            | Measuring time | 
            Approx. 30 second for earth resistance | 
        
        
            | Accuracy(Earth resistance) | 
            (23℃ ± 5℃, 85% RH or less) 
            Range/Resolution/Accuracy 
            10Ω/0.01Ω/0.1~1Ω :±0.1Ω、1~10Ω :±0.5Ω 
            300Ω/0.1Ω/10~50Ω :±2.0Ω、50~150Ω :±5.0Ω、150~200Ω :±20Ω、200~300Ω :±30Ω | 
        
        
            | Accuracy(AC current) | 
            (23℃ ± 5℃, 85% RH or less) 
            Range/Resolution/Accuracy 
            200mA/0.1mA/3% rdg ± 8dgt 
            2000mA/1mA/2% rdg ± 8dgt 
            20A/0.01A/2% rdg ± 8dgt | 
        
        
            | Measuring CT | 
            φ34mm with 2.5m lead | 
        
        
            | Injection CT | 
            φ34mm with 2.5m lead | 
        
        
            | Injection signal | 
            Approx. 160mVp-p, Auto sweep 4KHz~200kHz | 
        
        
            | Battery charger | 
            AC200V~240V (50/60Hz) | 
        
        
            | Memory function | 
            200 measuring data can be stored and displayed |