| Measuring function |
AC load current |
| Measuring method |
Dual slope integration mode |
| AC Conversion |
Average sensing rms reading |
| Display |
3.5 digit LCD max. reading of 1999 with annunciators |
| Measuring Range |
AC 0~20A/600A (50Hz/60Hz), 2 ranges manual |
| Structure |
Splash proof |
| Jaw opening capability |
φ35mm |
| Accuracy |
(23℃~40℃±5℃ 90%RH or less)
Range/Resolution/Accuracy(50/60Hz)
AC 20A/0.01A/±2%rdg±8dgt
AC 600A/1A/0~400A : ±2%rdg±8dgt 400A~600A : ±3%rdg±8dgt |
| Peak hold function |
LED lamp |
| Sampling time |
2 times/sec |
| Low battery indication |
"B" mark on LCD |
| Insulation Resistance |
100MΩ or more by DC 1000V insulation tester
(Between hot stick connector and core of CT) |
| Withstanding Voltage |
AC 100kV, 5 minute
(Between hot stick connector and core of CT) |
| Limitation of circuit voltage |
AC 80Vrms to 46KVrms
(Depend on the specification of hot stick) |
| Operating Temperature |
0~40℃, less than 90%RH (without condensation) |
| Power supply |
AAA size battery×2 |
| Size and Weight |
70(W)×290(H)×32(D)mm, Approx. 350gs. |
| Accessories |
Carrying case:1
Instruction manual:1
Batteries:2 |
| Option |
Hot stick |