Jaw opening capability |
40mm φ |
Limitation of circuit voltage |
Less than AC/DC 500V |
Accessories |
Carrying case:1
Instruction manual:1
Batteries:3
Voltage input cable with fuse(3m):1set |
Sampling rate |
1 time/sec. |
Display |
LCD max. 9999 count with annunciators |
Measuring function |
AC leakage current(Io)
AC Resistive leakage current (Ior) |
Measuring ranges |
0~10mA/100mA/1000mA (Io)
0~10mA/100mA (Ior) |
A/D Conversion |
Dual slope integration method |
Over range indication |
"OL" mark on LCD |
Data hold indication |
"DH" mark on LCD |
Low battery indication |
"Battery" mark on LCD |
Auto power off |
Approx. 10 minutes after power on |
Phase detection |
By voltage input |
Input frequency range |
45~65Hz (50 or 60Hz is selectable by switch) |
Withstanding Voltage |
AC 3700V/1 minute between CT and outer case |
Storage Temperature |
-10~60℃, < 70%RH (without condensation) |
Accuracy |
(23 ℃ ±5 ℃ , less than 85%RH)
Function/Range/Resolution/Accuracy
Ior/10mA/0.001mA/±1.5% rdg ± 10dgt
Ior/100mA/0.01mA/±1.2% rdg ± 10dgt
Io/10mA/0.001mA/±1.0% rdg ± 10dgt
Io/100mA/0.01mA/±1.0% rdg ± 10dgt
Io/1000mA/0.1mA/±1.0% rdg ± 10dgt |
Operating Temperature |
0~50℃, < 80%RH (without condensation) |
Power supply |
LR03,AM-4 or AAA size Alkaline battery×3 |
Dimension |
44(W)×200(H)×24(D)mm |
Weight |
Approx.210g |
AC Conversion |
Average sensing rms reading |