| Measuring Function |
AC Current and Power Flow Direction |
| Measuring Scope |
AC1A~600A 50/60Hz |
| Measuring Range |
60.0A/600A(Auto) |
| Accuracy |
±3%(full scale to each range) |
| Current Detection |
True RMS |
| Display |
AC Current:LCD Display
Flow Direction:LED (Red) blinking when reverse flow
|
| Record Contents |
Current Value/Flow Direction/Month:Date:Time |
| Record Interval |
0.5/1/5/30/60sec |
| Record Capacity |
Approx.. 690k data |
| Record Output |
Internally memorized and output to USB (CSV) |
| Capable Conductor |
Inside Diameter:φ9 ~ 25mm(Insulated) |
| Circuit Voltage |
AC7kV |
| Temp. Range(Accy) |
-10℃~+50℃ |
| -ditto- (Operation) |
-20℃~+60℃(Operation within ±6%F.S.) |
| Structure |
IEC529 IP64 |
| Power Supply |
AA size alkaline or lithium battery ×6 |
| Dimension/Weight |
W133×H365×D110mm approx.. 2.3kg |