Model: SX20NERTAR Specifications |
Load Rating |
20 amps @ 120 volts |
Power Requirement (no load) |
15 watts per circuit |
Surge Let- Through Voltage (6000-volt surge) |
1000 surges, 6000 volts, 3000 amps, B3 pulse; Measured suppressed voltage: 170 volts; no failures. |
UL 1449 Adjunct Classification Test Results |
Grade A, Class 1, Mode 1 (CID A-A-55818) |
Federal Guidelines |
Unlimited, due to current limiting (8 x 20 μs) |
EMI/RFI Filter, Normal Mode (50-ohm load) |
40 dB @ 100 kHz; 50 dB @ 300 kHz; 50 dB @ 3 MHz; 50 dB @ 30 MHz |
EMI/RFI Filter, Common Mode (50-ohm load) |
18 dB @ 300 kHz; 30 dB @ 1 MHz; 50 dB @ 5 MHz; 50 dB @ 20 MHz |
Maximum Applied Surge Voltage |
6000 volts* |
Maximum Applied Surge Current |
Unlimited, due to current limiting* |
Maximum Applied Surge Energy |
Unlimited, due to current limiting* |
Endurance (C62.41-1991 Category B3 pulses) |
1 kV>500,000; 3 kV>10,000; 6 kV>1000 |
Maximum Load Inrush Current During Power-up |
1000 Joules |
Remote Turn-on Applied Voltage Range |
11.375" W x 7.625" D x 1.8125" Contact Closure: 3 mA
5 V DC Applied Voltage: 1 mA
12 V DC Applied Voltage: 2.5 mA
24 V DC Applied Voltage: 5 mA |
Auxiliary Relay Contact Rating |
30 Volts at 1 Amp |
LED Output |
12 volts DC, maximum 20 mA (resistor required) |
Dimensions |
12.0" H x 12.0" W x 4.0" D (30.5 x 30.5 x 10.2 cm) |
Weight |
12 lbs (5.45 kg) |
Temperature Range |
5º to 35º C |
Humidity Range |
5% to 95% R.H., non-condensing |
Agency Listings |
ETL and cETL (UL 1449, 2nd edition; CSA C22.2 No.8-M1986, R2000) |
CE |
Directives 89/336/EEC, 92/31/EEC and 93/68/EEC EN 60950 EN55022: 1998 Class B |
FCC |
Part 15 Class B |
NETWORK |
Single 10/100 Unshielded Twisted Pair Ethernet Jack IP Addressed: DHCP Assigned or Static Internal HTTP Web Server Forms Processing Browser Required Internal Telnet Server |