            | Load Rating | 
            20 amps per circuit @ 120 volts(80 amps total) | 
        
        
            | Power Requirement (no load) | 
            15 watts per circuit | 
        
        
            | Surge Let- Through Voltage (6000-volt surge) | 
            1000 surges, 6000 volts, 3000 amps, B3 pulse; Measured suppressed voltage: 170 volts; no failures. | 
        
        
            | UL 1449 Adjunct Classification Test Results | 
            Grade A, Class 1, Mode 1 (CID A-A-55818) | 
        
        
            | Federal Guidelines | 
            Unlimited, due to current limiting (8 x 20 μs) | 
        
        
            | EMI/RFI Filter, Normal Mode (50-ohm load) | 
            40 dB @ 100 kHz; 50 dB @ 300 kHz; 50 dB @ 3 MHz; 50 dB @ 30 MHz | 
        
        
            | EMI/RFI Filter, Common Mode (50-ohm load) | 
            18 dB @ 300 kHz; 30 dB @ 1 MHz; 50 dB @ 5 MHz; 50 dB @ 20 MHz | 
        
        
            | Maximum Applied Surge Voltage | 
            6000 volts* | 
        
        
            | Maximum Applied Surge Current | 
            Unlimited, due to current limiting* | 
        
        
            | Maximum Applied Surge Energy | 
            Unlimited, due to current limiting* | 
        
        
            | Endurance (C62.41-1991 Category B3 pulses) | 
            1 kV>500,000; 3 kV>10,000; 6 kV>1000 | 
        
        
            | Maximum Load Inrush Current During Power-up | 
            N/A | 
        
        
            | Remote Turn-on Applied Voltage Range | 
            N/A | 
        
        
            | Auxiliary Relay Contact Rating | 
            N/A | 
        
        
            | LED Output | 
            12 volts DC, maximum 20 mA (resistor required) | 
        
        
            | Dimensions | 
            16.0" H x 12.0" W x 4.0" D (40.6 x 30.5 x 10.2 cm) | 
        
        
            | Weight | 
            30 lbs (13.6 kg) | 
        
        
            | Temperature Range | 
            5º to 35º C | 
        
        
            | Humidity Range | 
            5% to 95% R.H., non-condensing | 
        
        
            | Agency Listings | 
            ETL and cETL (UL 1449, 2nd edition; CSA C22.2 No.8-M1986, R2000) |