Measuring values |
temperature |
Output voltage |
TRV: 1x 0..10 V or 0..5 V, LCD/relay: 0..10 V or 0..5 V (live-zero can be configured via Thermokon USEapp), min. load 5 kΩ |
Output ampere |
TRA: 1x 4..20 mA, max. load 500 Ω |
Output passive |
depending on used sensor |
Output switch contact |
Relay: 2x floating contact NO for 24 V ~ or 24 V = / 3 A, (optional) |
Network technology |
LON FT (free topology), RS485 Modbus |
Power supply |
15..24 V = (±10%) or 24 V ~ (±10%) SELV, TRA: 15..24 V = (±10%) SELV, LCD/relay/BUS: 15..35 V = or 19..29 V ~ SELV |
Power consumption |
TRV: typ. 0,35 W (24 V =) | 0,82 VA (24 V ~), TRA: typ. 0,5 W (24 V =), LON: typ. 0,5 W (24 V =) | 1,7 VA (24 V ~), LCD/relay/BUS: max. 2,5 W (24 V =) | 4,3 VA (24 V ~) |
Measuring range temp. |
-50..+50 | -20..+80 | -15..+35 | -10..+120 | 0..+50 | 0..+100 | 0..+160 | 0..+250 °C, TRV | TRA: adjustable at the transducer, default setting: 0..+160 °C, LON: -45..+130 °C, LCD/relay/RS485 Modbus: can be configured via Thermokon USEapp, default setting: -20..+80 °C, passive: -50..+120|+150|+160|+260 °C, depending on used sensor |
Accuracy temperature |
measuring current typ. <1 mA, ±0,5 K (typ. at 21 °C within default measuring range), passive: ±0,3 K (typ. at 21 °C), depending on used sensor |
Sensor |
passive: 2-wire (standard), 3-wire or 4-wire |
Display |
LCD 29x35 mm with RGB backlight, (optional) |
Enclosure |
enclosure USE-S, LCD/relay/RS485 Modbus: enclosure USE-M, PC, pure white, LCD: cover PC, transparent, LON: PA6, pure white, with quick lock screws |
Protection |
IP65 according to EN 60529, SI-Protection (not possible for electronic Sensors) |
Cable entry |
M16 for wire max. Ø=8 mm, LON: M20 for wire max. Ø=8 mm, seal insert for double cable entry for wire max Ø=6 mm, Relay: M20 for wire max. Ø=8 mm incl. seal insert for double cable entry for wire max Ø=6 mm, BUS: M25 with fourfold cable entry for wire with max. Ø=7 mm, removable (all types enclosure USE) |
Connection electrical |
removable plug-in terminal, max. 2,5 mm², LON: terminal block, max. 1,5 mm², BUS terminal: removable plug-in terminal, max. 1,5 mm² |
Pocket |
stainless steel V4A, Ø=6 mm, mounting length: 50 | 100 | 150 | 200 | 250 | 300 | 450 mm |
Ambient condition |
enclosure: -35..+70 °C, max. 85% rH short term condensation, enclosure passive: -35..+90 °C, max. 85% rH short term condensation, mounting clip: -35..+90 °C |
Weight |
passive: 100 g, TRV/TRA: 115 g, LON: 160 g, RS485 Modbus: 120 g, LCD: 150 g |
Mounting |
with duct temperature of +90..+120 °C mounting flange MF6DS flexible, at +120..+260 °C mounting flange MF6 (brass) is recommended |
Delivery contents |
incl. mounting clip enclosure USE-S pure white, LCD/BUS/relay: incl. mounting flange MF6DS flexible |
|