Measuring values |
temperature |
Medium |
air |
Output switch contact |
single pole change over, switching capacity max. 10 A (250 V ~) |
Accuracy temperature |
repeatability ±0,5 °C |
Set point range |
-10..+12 °C (default +5 °C) |
Switching values |
switching differential: 2 °C ±1 °C |
Enclosure |
PA6 GK30, light grey, cover ABS, transparent |
Protection |
IP65 according to EN 60529 |
Cable entry |
M16 for wire max. Ø=8 mm |
Connection electrical |
terminal block, max. 2,5 mm² |
Capillary pipe |
copper with tube filling R507, length 1,8 | 3 | 6 | 12 m, sensor operating length approx. 600 mm, contact material Ag/Ni (90%/10%), gold plated (3 µm) |
Ambient condition |
-35..+70 °C, max. 85% rH short term condensation |
Delivery contents |
Installation set TFR/MWF with PA6 GF30 (6 pcs) |
|