Type
|
Portable Circuit Breaker Analyzer
|
Physical specifications
|
14”W x 21 K” L x 8” D (35 cm x 53 cm x 20 cm. 15 lbs (6.8 Kg)
|
Input power
|
100-240Vac, 3A, 50/60Hz
|
Dry-contact inputs
|
3 channels (9021-UC) or 6 channels (9100-UC). Channel can detect the main contact and resistor contact time.
|
Timing windows
|
1 second, 10 seconds, or 20 seconds
|
Timing resolutions
|
±50 micro-seconds @ 1 sec. duration, ±500 micro-seconds @ 10 sec. duration, ±1.0 milli-seconds @ 20 sec. duration
|
Timing accuracy
|
0.05% of reading ±0.05 ms @ 1 second duration
|
Dry-contact cannel protection
|
All contact inputs are grounded until test. Input channels are also protected against static discharge
|
Dry-contact detection range
|
Closed: Less than 20 Ohm. Opened: greater than 5000 ohm
|
Insertion resistor detection range
|
50 - 5,000 ohms
|
Trigger input voltage
|
Open/Close trigger voltage: 24 V – 300V DC or peak AC
|
Voltage sensing input range
|
V1: analog input; 0 ¬ 250 V DC or peak AC; sensitivity ±1 V; record and print voltage level
V2 and V3: voltage presence/absence detector input; 24 ¬ 255 V DC or peak AC; record and print 3 timing events
|
Breaker operations
|
Initiate Open, Close, Open-Close, Close-Open, Open-Close-Open
|
Breaker initiate capacity
|
30A, 250 Vac/dc max
|
Initiate current reading range
|
one, non-contact, Hall-effect sensor, 0 ¬ 20 amp range, dc to 5 Khz AC
|
Digital travel transducer inputs
|
3 digital travel transducer channels; linear range: 0.0 ¬ 60.0 in (±0.01 in) rotary range: 0 ¬ 360 degrees (±0.36 degrees)
|
Resistor type transducer inputs
|
3 channels, 200 ohm – 10K ohms
|
Contact travel point difference
|
Measures “slow-close” contact-point distances; results can be printed
|
Display
|
Back-lit LCD screen (128 x 240 pixels); viewable in bright sunlight and low light
|
Printer
|
Built-in 4K” wide thermal printer that can print both graphic contact travel waveforms and tabulated test results
|
Internal test record storage
|
Store up to 200 test records and 100 test plans
|
External test record storage
|
USB Flash drive interface for external storage of test records and test plans
|
Computer interfaces
|
One USB port, optional Bluetooth wireless interface
|
Pc software
|
Windows® based Breaker Analysis software included with purchase price
|
Cables
|
Furnished with full set of test leads
|
Options
|
Transportation cases (available for the CBT-7000 and travel transducers), on-line timing mode, dual ground testing mode, bluetooth interface
|
Safety
|
Designed to meet UL 6101A-1 and CAN/CSA C22.2 No 1010.1-92 standards
|
Environment
|
Operating: -10°C to +50°C (+15°F to +122°F); Storage: -30°C to +70°C (-22°F to +158°F)
|
Humidity
|
90% RH @ 40°C (104°F) non-condensing
|
Altitude
|
2,000 m (6,562 ft) to full safety specifications
|
Warranty
|
One year on parts and labor
|
Optional Testing Features
|
|
ON-LINE TIMING MODE
|
On-line current sensor
|
Three non-contact AC current sensors, range 0-100 amperes
|
On-line dc current sensor
|
One non-contact DC current sensor, range 0-20 amperes
|
|
DUAL GROUND TIMING MODE
|
Dual ground clamp-on probes
|
3 non-contact clamp-on probes
|