- The TTRF-250 is Amperis' fourth generation transformer turns ratio tester. This latest design provides a higher turns-ratio test voltage of 250Vac, provides a wireless Bluetooth PC interface, and features a 44-key "QWERTY"-style membrane keyboard. All these features greatly improve the accuracy of the turns ratio readings, ease of operation, and reliability.
- The TTRF-250 determines the turns ratio of the transformer under test using the IEEE C57.12.90 measurement method. The turns-ratio range is from 0.8 to 50,000 to 1. Transformer turns ratio, excitation current, and winding polarity are displayed on the built-in 128 x 64 pixels graphic LCD screen. The TTRF-250 can be used as a standalone unit or can be computer-controlled.
Thông số kỹ thuật
TTRF-250’s Specifications
|
Type
|
Portable, lightweight, automatic, 3-phase transformer turns-ratio meter
|
Physical specifications
|
18”W x 5”H x 12”D (45.7 cm x 12.7 cm x 30.5 cm ); Weight: 20 lbs (9.1 kg)
|
Input power
|
100 - 240 Vac, 50/60 Hz
|
Measurement method
|
ANSI/IEEE C57.12.90
|
Ratio measuring range
|
0.8 - 50,000 to 1
|
Turns ratio accuracy
|
0.8 - 1,999: ±0.1%, 2,000 - 3,999: ±0.25%. 4,000 - 14,999: ±1%, 15,000 - 50,000: ±2% @ 4Vac
0.8 - 1,999: ±0.1%, 2,000 - 3,999: ±0.20%. 4,000 - 14,999: ±1%, 15,000 - 50,000: ±1.5% @ 40Vac
0.8 - 1,999: ±0.1%, 2,000 - 3,999: ±0.20%. 4,000 - 14,999: ±1%, 15,000 - 50,000: ±1.5% @ 100Vac
0.8 - 1,999: ±0.1%, 2,000 - 3,999: ±0.15%. 4,000 - 14,999: ±0.8%, 15,000 - 50,000: ±1.2% @ 250Vac
|
Test voltages
|
4 Vac @ 1 Amp, 40 Vac @ 200 mA, 100 Vac @ 100 mA, 250 Vac @ 50 mA
|
Excitation current reading range
|
0 - 2 Amperes; Accuracy: ±1mA, ±2% of reading (±1 mA)
|
Phase angle measure
|
0 - 360 degrees; Accuracy: ±0.2 degrees ( ±1 digit)
|
Display
|
Back-lit LCD screen (128 x 64 pixels) viewable in bright sunlight and low-light levels
|
Printer
|
Built-in 4.5-inch wide thermal printer
|
Computer interface
|
Bluetooth, USB port
|
External data storage
|
One USB Flash drive interface port; Up to 999 transformer test records can be stored on a USB Flash drive (not included)
|
Pc software
|
Windows®-based Transformer Turns-Ratio Analyzer application is included
|
Internal test record storage
|
Can store 112 transformer test records internally. Each record holds the test record header and up to 99 readings.
|
Internal test plan storage
|
Can store 128 transformer test plans internally. Test plans can be transferred to the unit from the PC via the Bluetooth/USB port or via the USB Flash drive interface
|
Load tap changer contact
|
240 Vac, 2 Amps
|
Safety
|
Designed to meet UL 61010A-1 and CAN/CSA C22.2 No. 1010.1-92 standards
|
Environment
|
Operating: -10°C to +50°C (+15°F to +122°F); Storage: -30°C to +70°C (-22°F to +158°F)
|
Humidity
|
90% RH @ 40°C (104°F) non-condensing
|
Altitude
|
2000 m (6,562 ft) to full safety specifications
|
Cables
|
One 15-foot single-phase set, one 15-foot 3-phase set, one 25-foot extension set, one safety ground, one USB, cable bag
|
Optional accessories
|
Transportation case
|
Warranty
|
1 year on parts and labor
|
|