The Beacon 410 is a highly configurable, microprocessor-based, flexible and easy to use 4 channel gas monitor. It simultaneously displays the gas type, readings, and status for 4 channels of gas detection. It can monitor any combination of direct connect sensors (LEL combustibles, Oxygen, Hydrogen Sulfide, Carbon Monoxide, and Carbon Dioxide) as well as any 4-20mA transmitters.
Each channel has 3 fully configurable alarm points. A built-in silenceableaudible alarm alerts you to alarm conditions. Each channel also has 2 dedicated fully configurable relays and there is a bank of common relaysas well. The common relays can optionally be configured as additional channel relays allowing up to 3 alarm relays per channel.
Each channel provides a 4-20mA output signal. A digital Modbus interface for remote logging of data via a Modbus network is standard. A Min-Max feature retains high & low peak readings for review at any time.
Field calibration is made simple by the easy to use Calibration Mode. A fully configurable high visibility strobe is available as an option. The unit can be powered from 115/220 VAC, an external 24 VDC source, or a 24 VDC backup battery. A trickle charging battery backup feature is also available as an option.
All features and functions of the Beacon 410 are controlled by easy to use menus on the backlit LCD display. The form-C (SPDT) relay contacts are rated at 10A, 250V, reducing or eliminating the need for additional slave relays. All features of the Beacon 410 are built into the unit so you never need to purchase or maintain any “add-on” cards or components.
Features
- Simultaneously monitor up to 4 channels
- Digital display of all 4 channels
- Accepts direct connect sensors for LEL / O2 / H2S / CO / CO2
- Accepts any 4-20 mA transmitter, 2 or 3 wire
- 3 programmable alarm levels per channel
- Up to 3 configurable alarm relays per channel
- Zero follower automatically compensates sensor drift
- 4-20 mA analog & Modbus digital output standard
- 115 / 220 VAC or 24 VDC operation
- Audible alarm with silence feature
- Alarm reset switch
- Built in trouble alarm with relay
- Weather proof NEMA 4X enclosure
- Optional strobe & battery backup available
Applications
- Petrochemical plants
- Refineries
- Water & wastewater treatment pants
- Pulp & paper mills
- Gas, telephone, & electric utilities
- Parking garages
- Manufacturing facilities
- Steel
- Automotive
- HVAC
Specifications
Physical
|
|
Dimensions |
Height: 12.5”
Width 11”
Depth 6.4” |
Enclosure |
NEMA 4X non-metallic for indoor and outdoor locations |
Conduit
Connection
|
3/4” NPT conduit hubs, 4 provided, for sensor, power, & relay wiring |
Wiring
Termination
|
Screw type terminal block, 14 gauge max |
Power
|
115 VAC & 220 VAC, or 24 VDC nominal, battery backup option available |
Controls
|
Display PCB Control Switches:
- UP/YES push button switch
- DOWN/NO push button switch
- ESCAPE push button switch
- ENTER push button switch
- External reset switch
- On/Off toggle switch
|
|
|
Environmental
|
|
Operating Temp |
-4°F to 122°F (-20°C to 50°C) |
Storage Temp |
-4°F to 158°F (-20°C to 70°C) |
Relative
Humidity |
0 - 95% RH (non-condensing) |
Enclosure
Rating |
NEMA-4X enclosure, chemical and weather resistant |
|
|
Inputs
|
|
Direct Wired
Sensors |
LEL, Oxygen, Carbon Monoxide, Hydrogen Sulfide, and Carbon Dioxide.
Remote amp not required for less than 500 feet |
4-20 mA Sensors |
Accepts any 4-20 mA transmitter (24 VDC, 2 or 3 wire). A wide variety of RKI/Riken sensors are available with 4-20 mA signals. Wiring distances up to 8,000 feet |
Sampling Methods |
Diffusion and sample draw heads available |
|
|
Outputs
|
|
Relays |
Two flexible, programmable Form-C (C, NO, NC) relays per channel, plus five common relays (Fail, Alarm-1, Alarm-2, Alarm-3, Alarm-Any). Common relays may optionally be assigned to function as additional channel alarm relays, providing for up to three alarm relays per channel. 10A contact rating. |
4-20 mA |
Signal output, 4-20 mA (maximum load impedance 500 ohms), per channel |
RS-485 |
Modbus format RS-485 serial output of all channel data, including gas reading and alarm status. |
Display |
4 x 20 backlit LCD display |
Audible |
Built-in audible alarm, 94 dB, mounted on enclosure
Coded output: pulsing = gas alarm, steady = fail |
Visual |
1. Alarm LEDs (on Display PCB)
- Alarm 1, yellow
- Alarm 2, orange
- Alarm 3, red
- Fail, yellow
2. Green Pilot LED to indicate AC power connected (on Display PCB)
3. An optional 24 VDC NEMA 4X strobe mounted to top of case. |
|
|
Warranty
|
One year materials and workmanship |
Partial List Of Detectable Gases
Many other gases or ranges available. Contact RKI for gases or ranges not listed. |
Ammonia (NH3)
|
0 - 75.0 ppm |
Arsine (AsH3 ) |
0 - 0.20 ppm |
Boron Trichloride (BCl3) |
0 - 15.0 ppm |
Carbon Dioxide (CO2) |
0 - 1.0 % |
Carbon Monoxide (CO) |
0 - 300 ppm |
Chlorine (Cl2) |
0 - 3.0 ppm |
Chlorine Dioxide (ClO2) |
0 - 1.00 ppm |
Chlorine Trifluoride (ClF3) |
0 - 1.00 ppm |
Combustibles |
0 -100% LEL |
Diborane (B2H6) |
0 - 30.0 ppm |
Fluorine (F2) |
0 - 6.0 ppm |
Hydrogen (H2) |
0 - 2000 ppm |
Hydrogen Chloride (HCl) |
0 - 15.0 ppm |
Hydrogen Fluoride (HF) |
0 - 9.0 ppm |
Hydrogen Sulfide (H2S) |
0 -100.0 ppm |
Nitric Oxide (NO) |
0 -100.0 ppm |
Nitrogen Dioxide (NO2) |
0 - 15.0 ppm |
Nitrogen Trifluoride (NF3) |
0 - 30.0 ppm |
Oxygen (O2) |
0 - 25.0 % |
Ozone (O3) |
0 - 1.0 ppm |
Phosphine (PH3) |
0 - 1.0 ppm |
Silane (SiH4) |
0 - 15.0 ppm |
Sulfur Dioxide (SO2) |
0 - 30.0 ppm |
TEOS (Si(OC2H5)4) |
0 -15/30 ppm |
Specifications subject to change without notice.
Made in the USA
|