Type
|
250 Ampere current source
|
Physical specifications
|
17"W x 12K"H x 10K"D (42.6 cm x 32cm x 27 cm). Weight: 46 lbs (21 kg)
|
Input power
|
100 - 120 Vac or 200 - 240 Vac (factory pre-set), 50/60 Hz
|
Output currents
|
0 - 5 A @ 120 Vac max; 0 - 25 A @ 24 Vac max; 0 - 120 A @ 6 Vac max; 0 - 250 A @ 3 Vac max
|
Internal current meter
|
100 mA - 1000 A; Accuracy: 1% of reading ±20mA
|
Measurement method
|
Isolated CT
|
External meter range
|
10 mA - 10 A; Accuracy: 1% of reading, ±2mA
|
Timer reading range
|
1ms - 2 hours; Accuracy: 0.1% of reading ±1ms
|
Timer stop inputs
|
Voltage input (24V - 300V, DC or peak AC), dry contact input, or removal of primary current
|
Display
|
Back-lit LCD Screen (20 characters by 4 lines); viewable in bright sunlight and low-light levels
|
Computer interface
|
RS-232C port for factory calibration and diagnostics
|
Safety
|
Designed to meet IEC61010 (1995), UL61010A-1, CSA-C22.2 standards
|
Environment
|
Operating: -10°C to +50°C (+15°F to +122°F); Storage: -30°C to +70°C (-22°F to +158°F)
|
Humidity
|
90% RH @ 40°C (104°F) non-condensing
|
Altitude
|
2,000 m (6,562 ft) to full safety specifications
|
Cables
|
Power cord, ground cable, 10-foot #2 AWG test leads
|
Options
|
Transportation case
|
Warranty
|
1 year on parts and labor
|