Type
|
100 - 600 Amp current source
|
Physical specifications
|
17”W x 12½”H x 10½”D, (42.6 cm x 32 cm x 27 cm); Weight: 46 lbs (21 kg)
|
Input power
|
100 - 120 Vac or 200 - 240 Vac (factory pre-set), 50/60 Hz
|
Internal meter range
|
100 mA - 1000 A; Accuracy: 1% of reading, ±20 mA
|
Measuring method
|
Isolated CT
|
External meter range
|
10 mA - 10 A; Accuracy: 1% of reading, ±2 mA
|
Measuring method
|
Isolated CT
|
Timer reading range
|
1 ms - 2 hours; Accuracy: 0.1% of reading ±1 ms
|
Timer stop input
|
Voltage input (24 - 300 V, DC or peak AC), dry-contact input, or removal of primary current
|
Computer interface
|
RS-232C port (19,200 baud) for factory calibration and diagnostics
|
Safety
|
Designed to meet IEC61010 (1995), UL 61010A-1, CSA-C22.2 standards
|
Environment
|
Operating: -10°C to +50°C (+15°F to +122°F); Storage: -30°C to +70°C (-22°F to +158°F)
|
Humidity
|
90% RH @ 40°C (104°F) non-condensing
|
Altitude
|
2,000 m (6,562 ft) to full safety specifications
|
Included Accessories
|
10-foot #1/0 AWG test leads, power cord, ground cable
|
Optional accessories
|
Transportation case
|
Warranty
|
1 year on parts and labor
|