• 100 A Digital micro-ohmmeter
• Alphanumerical display
• Resolution: 0.1 µΩ
• Resistance reading: up to 200 Ω
• Up to 100 A test current
• Rechargeable battery
• Kelvin-type (4-wires) measurement
• Powered by internal battery (up to 10 A) or mains supply
• Direct reading (Up to 4½ digits)
• Overheating Protection
Test currents
1 mA, 10 mA, 100 mA, 1 A, 10 A, 100 A.
Each current may be continuously adjustable from 0 to 100%.
Resistance ranges
0-2000 µΩ @ 100 A.
0-20 mΩ @ 10 A.
0-200 mΩ @ 1 A.
0-2000 mΩ @ 100 mA.
0-20 Ω @ 10 mA.
0-200 Ω @ 1 mA.
Resolution
0.1 µΩ @ 100 A.
1 µΩ @ 10 A.
10 µΩ @ 1 A.
100 µΩ @ 100 mA.
1 mΩ @ 10 mA.
10 mΩ @ 1 mA.
Measurement Principle
Four-terminal, Kelvin-type.
Continuous operation time
At 100 A this equipment may be used continuously for aprox. 15 minutes before the thermal protection activates.
At 10 A or less, there is not a limited time for continuous operation.
Basic accuracy
R < 0.5 mΩ: ± (0.50% of reading + 2 UUD*).
R ≥ 0.5 mΩ: ± (0.20% of reading + 2 UUD*).
* Units of the Least Significant Digit.
Advanced features
Digital direct reading of low resistances in the alphanumerical display, with up to 4½ digits. Very fast and accurate measurements.
Thermal protection
Protects all sensitive components, avoiding any damage due to overheating.
Environmental protection
IP54 with closed lid.