The newly redesigned Eagle 3X Combustion System Analyzer eliminates the number one hassle for combustion contractors; the annual replacement and calibration of the O2 sensor. By replacing the electro chemical O2 sensor with the EOS Technology CO2 sensor, the EAGLE 3X now takes direct CO2 measurements and calculates the O2 level.

Liên Hệ Hỗ Trợ

    • SĐT: 0984 843 683

    • Mail: info@ttech.vn

      • Zalo: 0984.843.683

Thông tin sản phẩm

Features


Heat exchanger test
CO data logger
Low battery indicator
Real time clock
High level CO alarm
Worklight
4 line backlit LCD display
179 memory positions
User customizable auxiliary screen
Individual report printouts
Time and date stamp
Rotary style selector
Protective boot with integral magnet
Gas Zero †
CO readings as low as 1 ppm
Field replaceable sensors (USA ONLY)
5 year limited warranty (including sensor)


Measures CO2 (EOS Technology)
CO (Long Life Sensor)
Inlet Temp/Flue Temp
Hi-Res Differential Manometer (select 0.01”/0.001”wc)
NO (EAGLE 3X: installed, EAGLE 2X: available as upgrade)
Calculates O2
Net Temp
Efficiency
Excess Air
Differential Temp (T1-T2)
Differential Pressure (P1-P2)
PreProgrammed Fuels Natural Gas
Propane
Heavy Oil
Light Oil
Bio Fuel
Wood
Eagle X Model C155 C157
Temperature Measurement
Flue Temp Range 20~2400°F (-29~1315°C)
Inlet Temperature (probe - T2) 20~2400°F (-29~1315°C)
Inlet Temperature (ambient) 32~112°F (0~50°C)
Net Temperature (ΔT)** 20~2400°F (-29~1315°C)
Resolution 0.1°C/F
Flue (T1, Inlet T2 & ΔT) Accuracy ±(0.3% rdg +3.6°F(2°C))
Inlet Temperature Accuracy ±(0.3% rdg +1.8°F(1°C))
Gas Measurement
Oxygen 0~21%**
O2 resolution / accuracy 0.1% / ±0.3%
Carbon Monoxide (CO) 0~2000 ppm (4000 max 15 min)*
CO resolution / accuracy 1 ppm / ±10 ppm<100ppm,
±5% rdg>100ppm
Carbon Dioxide (CO2) 0~20%*
CO2 resolution / accuracy 0.1% / ±2%
Efficiency** 0~99.9%**
Efficiency resolution/accuracy 0.1% / ±3%
Excess Air** 0~250%**
Excess Air resolution/accuracy 0.1% / ±3%
CO/CO2 ratio** 0~0.999
CO/CO2 resolution/accuracy 0.001 / ± 5% rdg
Nitric Oxide (NO1)*** - 0~100 ppm
NO1 resolution/accuracy*** - ±2 ppm<30ppm
±5ppm<100 ppm
Pressure (Differential)
Range ±0.08” wc (±0.2mBar)
±0.4” wc (±1mBar)
±32” wc (±80mBar)
Accuracy 2±0.002” wc (±0.005mBar)
±0.01” wc (±0.03mBar)
±3% rdg
Pressure Resolution
Resolution 0.001” wc < 9.999” wc
0.01” wc >10.00” wc
0.001mBar<24.999mBar
0.01mBar > 25 mBar
* Measured at STP (standard temperature and pressure) 0.01” wc >10.00” wc
** Calculated value
*** NO1 sensor installed on C157. Available as an upgrade for C155.

† Gas Zero (Fresh Air Zero) - Is a reset procedure to maintain accurate readings from the EOS sensor. This procedure compensates for any change in ambient conditions that may impact the readings.