High Voltage burning unit SVP-05C is designed for burning (destroying the soldered joint with resistance close to zero, in the point where a high voltage cable core short circuits to the shell or another core) the defective insulation of power cables, with subsequent afterburning, in order to destroy the contact resistance in the defective point, which allows for subsequent application of the known methods for determining the distance to the fault and fault location directly on the cable track.
- Technical Specifications
Characteristic |
Value |
Single-phase AC power supply voltage, V |
220±22 |
Power supply frequency, Hz |
50±1 |
Maximum output voltage with no load, kV |
25 |
The number of working intervals |
6 |
The maximum output current under short-circuit for high voltage intervals, A, at least |
7 |
Maximum output current for short-circuit for low-voltage interval of "500 V", A, no less |
15 |
Longest allowed continuous operation time, min, with load current of:
|
100% of maximum |
10
|
70% of the maximum |
30 |
Current consumption, A, max |
40 |
Average lifespan, years
|
10 |
Dimensions, mm |
820x630x500 |
Net weight, kg, max |
200 |
- Operating Conditions
The device is designed for an indoors operation under the following conditions:
Condition |
Value |
Air temperature, °С |
from -10 to +40
|
Relative humidity, %, up to |
80 at +25° С |
Atmospheric pressure, kPa (mm hg) |
84,0 – 106,7 (630 – 800) |
|