Hotline: 0984.843.683 Email: info@ttech.vn  Zalo: 0984.843.683

Xe thử nghiệm cáp ngầm ETL-35 KEP

Mã sản phẩm: ETL-35
Sử dụng cho Model:
Hãng SX: KEP
Xuất xứ
Bảo hành
Tình trạng

Tình trạng: Còn hàng

Đặt hàng
Cable Test Van

Liên Hệ Hỗ Trợ

    • SĐT: 0984 843 683

    • Mail: info@ttech.vn

      • Zalo: 0984.843.683

Thông tin sản phẩm

Cable test van ETL-35 is a combination of testing equipment mounted in a van and designed to perform the following:

  • High-voltage testing with AC voltage of up to 100 kV;
  • High-voltage testing with DC voltage of up to 60 kV;
  • Measuring the parameters of power transformers using the low-voltage tester BNI;
  • Determining the capacitance and dissipation factor of electrical facilities with voltages of up to 10 kV.

The price of ETL-35 incudes the trainging of the Customer's personnel. ETL-35 manufacturing time is 30 days.


  • Technical Specifications

    General ETL-35 specifications:

    Characteristic Value
    Single-phase AC power supply voltage, V 
    220±22 
    Power supply frequency, Hz
    50±2
    Consumed current, A, max
    80
    Net weight, kg, max 700
    Operating personnel, people, min 2
    Lifespan, years, min 10

     

    High voltage tester BVI based on the current transformer IOM-100/16specifications:

    The unit is intended for testing the insulation of power cables and solid dielectric with the rectified voltage of up to 60 kV, as well as for testing solid dielectrics with sinusoidal voltage of up to 100 kV (RMS) at 50 Hz.

    Characteristic Value
    Maximum rectified voltage under continuous running duty, kV 
    60
    Maximum running current under rectified voltage, mA 100
    Maximum AC voltage (RMS), kV 100
    Maximum operating current under AC voltage (RMS), mA 
    100
    Dimensions, mm, max 650x84
    Net weight, kg, max 220


    Dissipation factor meter IDP-10 specifications:

    IDP-10 measures a capacity and dissipation factor of objects at the AC voltage of 10 kV at 50 Hz within the limits established by the AC bridge SA-7100/2.

    Characteristic Value
    Maximum AC voltage (RMS), kV
    10
    Reduced AC voltage measurement error, %, max
    3
    Dimensions, mm, max 220х300х350
    Net weight, kg, max 5

     

    High potential DC current meter ITVC-20 specifications:

    ITVC-20 is designed for measuring the DC current of the negative polarity in the circuits with the potential of up to 60 kV with respect to the ground.

    Characteristic Value
    Measurements range, mA
    0.1 ... 20
    Maximum relative measurement error in a given range
    3
    Maximum multiplication factor of the microammeter overloading
    3.5
    Maximum allowed potential of device casing with respect to the ground, kV 60
    Voltage drop between the device's terminals, V
    2
    Dimensions, mm, max 165х100
    Net weight, kg, max