MAIN FEATURES  
DC cable testing up to 40 kV with 300 mA max. current;
Burning up to 20 kV / 1 A;
Surge energy up to 2400 J;
Precise fault prelocating using Time‑Domain Reflectometer RIF‑9 working in:
TDR mode;
Arc-Reflection mode;
Impulse Current Mode;
Voltage coupling mode;
Automatic test procedure;
Fault location using step voltage mode (optional).
 
 
ADVANTAGES 
Easy user friendly interface;
High safety level;
Multistep self fault protection;
Flexible auxiliary equipment integration.
 
 
    - Technical Specifications
 
     
    
    
     
     
    - Operating Conditions
 
    
    
    The cable test van is designed for an outdoors operation under the following conditions: 
    
     
        
            
                | Condition | 
                Value | 
             
            
                | Air temperature, °С | 
                from -20 to +40 
                 | 
             
            
                Relative humidity, %, up to 
                 | 
                80 at +20° С | 
             
            
                Atmospheric pressure, kPa (mm hg)  
                 | 
                84,0 – 106,7 (630 – 800) | 
             
        
     
    
    Operating ETL-40V in explosive environments is strictly prohibited! 
     
     
 
    
        
            | Parameter | 
            Value | 
         
        
            | TEST MODE | 
         
        
            | DC voltage range | 
            0 – 40 kV  | 
         
        
            | DC current, max | 
            300 mA  | 
         
        
            | Measuring uncertainty | 
             less than 3 % | 
         
        
            | BURN MODE | 
         
        
            | DC voltage range | 
            0 – 20 kV 
             | 
         
        
            | DC current, max | 
            1 A | 
         
        
            | Measuring uncertainty | 
            less than 3 % | 
         
        
            | SURGE MODE | 
         
        
            | Stages | 
            4; 8; 16; 32 kV | 
         
        
            | Max. surge energy | 
            2400 J (at 4 kV stage);  
            2000 J (at 8/16/32 kV stages) | 
         
        
            | Timer set (automatic surge mode) | 
             5 – 15 seconds | 
         
        
            | Manual single surge | 
             yes | 
         
        
            | Flexible voltage change during automatic operation | 
             yes | 
         
        
            Pinpointing with an acoustic receiver 
             | 
             yes | 
         
        
            | PRELOCATION MODE | 
         
        
            | Methods | 
            TDR; Arc reflection;Impulse current; Voltage coupling | 
         
        
            | Automatic distance measuring | 
            yes | 
         
        
            | Saving cable parameters into Reflectometer non‑volatile memory | 
            yes | 
         
        
            | Saving reflectograms either to Reflectometer non-volatile memory or USB flash drive | 
            yes | 
         
        
            | CABLE TRACING MODE | 
         
        
            | Cable tracing using 50W audio-frequency generator with frequencies 491/ 982/ 8446 Hz with a receiver | 
            yes | 
         
    
  
                             |