MAIN FEATURES  
DC cable testing up to 8 kV;
Cable faulty place burning;
Precise fault prelocating using Time‑Domain Reflectometer RIF‑9;
Precise pinpointing with ground microphone;
Cable route tracing (optional).
 
 
ADVANTAGES 
Easy user friendly interface;
High safety level;
Multistep self fault protection;
Flexible auxiliary equipment integration.
 
 
 
 
    - Technical Specifications
 
     
    
    
     
     
    - Operating Conditions
 
    
    
    The cable test van is designed for an outdoors operation under the following conditions: 
    
     
        
            
                | Condition | 
                Value | 
             
            
                | Air temperature, °С | 
                from -20 to +40 
                 | 
             
            
                Relative humidity, %, up to 
                 | 
                80 at +20° С | 
             
            
                Atmospheric pressure, kPa (mm hg)  
                 | 
                84,0 – 106,7 (630 – 800) | 
             
        
     
    
    Operating ETL-8V in explosive environments is strictly prohibited! 
     
     
 
    
        
            | Parameter | 
            Value | 
         
        
            | GENERAL parameter | 
         
        
            | Input voltage, V | 
            230 ± 23 | 
         
        
            | Frequency, Hz | 
            50 ± 1 | 
         
        
            | Power consumption, kVA, max | 
            1.5 | 
         
        
            | TEST MODE | 
         
        
            | Output DC voltage range, kV | 
            0 – 8 
             | 
         
        
            | Output DC current range, mA | 
            0 – 10  
             | 
         
        
            | BURN MODE | 
         
        
            Output DC voltage range, kV 
             | 
            0 – 8 
             | 
         
        
            | Output DC current range, mA | 
            0 – 100 
             | 
         
        
            | SURGE MODE | 
         
        
            | DC voltage ranges, kV | 
            2 / 4 / 8 
             | 
         
        
            | Output energy, J, max | 
            1000 | 
         
        
            | Timer set (automatic surge mode), seconds | 
            3 – 15 
             | 
         
        
            | Manual single surge | 
             yes | 
         
        
            | Flexible voltage change during automatic operation | 
             yes | 
         
        
            Pinpointing with an acoustic receiver 
             | 
             yes | 
         
        
            | PRELOCATION MODE | 
         
        
            | Methods | 
            TDR / Arc reflection / Impulse current / Voltage coupling 
             | 
         
        
            | Automatic distance measuring | 
            yes | 
         
        
            | Saving cable parameters into Reflectometer non‑volatile memory | 
            yes | 
         
        
            | Saving reflectograms either to Reflectometer non-volatile memory or USB flash drive | 
            yes | 
         
        
            | CABLE TRACING MODE | 
         
        
            | Cable tracing using 50W audio-frequency generator with frequencies 491/ 982/ 8440 Hz with a receiver | 
            yes | 
         
    
  
                             |