MAIN FEATURES
DC cable testing up to 8 kV;
Cable faulty place burning;
Precise fault prelocating using Time‑Domain Reflectometer RIF‑9;
Precise pinpointing with ground microphone;
Cable route tracing (optional).
ADVANTAGES
Easy user friendly interface;
High safety level;
Multistep self fault protection;
Flexible auxiliary equipment integration.
- Technical Specifications
- Operating Conditions
The cable test van is designed for an outdoors operation under the following conditions:
Condition |
Value |
Air temperature, °С |
from -20 to +40
|
Relative humidity, %, up to
|
80 at +20° С |
Atmospheric pressure, kPa (mm hg)
|
84,0 – 106,7 (630 – 800) |
Operating ETL-8V in explosive environments is strictly prohibited!
Parameter |
Value |
GENERAL parameter |
Input voltage, V |
230 ± 23 |
Frequency, Hz |
50 ± 1 |
Power consumption, kVA, max |
1.5 |
TEST MODE |
Output DC voltage range, kV |
0 – 8
|
Output DC current range, mA |
0 – 10
|
BURN MODE |
Output DC voltage range, kV
|
0 – 8
|
Output DC current range, mA |
0 – 100
|
SURGE MODE |
DC voltage ranges, kV |
2 / 4 / 8
|
Output energy, J, max |
1000 |
Timer set (automatic surge mode), seconds |
3 – 15
|
Manual single surge |
yes |
Flexible voltage change during automatic operation |
yes |
Pinpointing with an acoustic receiver
|
yes |
PRELOCATION MODE |
Methods |
TDR / Arc reflection / Impulse current / Voltage coupling
|
Automatic distance measuring |
yes |
Saving cable parameters into Reflectometer non‑volatile memory |
yes |
Saving reflectograms either to Reflectometer non-volatile memory or USB flash drive |
yes |
CABLE TRACING MODE |
Cable tracing using 50W audio-frequency generator with frequencies 491/ 982/ 8440 Hz with a receiver |
yes |
|