| Measured Variables | 
        
            | Relative Humidity | 
        
            | Measuring Range | 0 – 100% RH | 
        
            | Accuracy with regard to works standards, including non-linearity, hysteresis and repeatability
 | At 20°C: ±1% RH (0 – 90% RH); ±1.7% RH (90 – 100% RH) At -20 to +40°C: ±(1.0 + 0.8% of measurement) % RH
 At -40 to -20°C, 40 to 180°C: ±(1.5 + 1.5% of measurement) % RH
 | 
        
            | Uncertainty of factory calibration1(20°C) | For 0 – 40% RH: ±0.6% RH For 40 – 97% RH: ±1.0% RH
 | 
        
            | Sensors | For general applications: HUMICAP® 180R With heated probe: HUMICAP® 180RC
 | 
        
            | Response time (t0.9) at 20°C in stationary air | With grid filter: 8sec With st. steel mesh filter: 20sec
 With sintered filter: 40sec
 | 
        
            | Temperature | 
        
            | Measuring range for type | 907023/331: -40 to +60°C 907023/333: -40 to +80°C/+120°C
 907023/334, 907023/335, 907023/337, 907023/338: -70 to +180°C
 | 
        
            | Temperature Sensor | Pt100 to EN 60 751 | 
        
            | Accuracy at 20°C | ±0.2°C 
  Accuracy over the entire range
 | 
        
            | Derived variables (option) | dew point temperature (Td), mixing ratio (x), absolute humidity (a), wet bulb temperature (Tw), enthalpy (h), water vapor pressure (pw)
 | 
        
            | Operating Conditions | 
        
            | Operating temperature range at | Probes: as measuring ranges Electronics: -40to +60°C
 With LC display: 0 to 60°C
 907023/334: 0 – 10MPa (0 – 100bar)
 907023/338: 0 – 4MPa (0 – 40bar)
 907023/333, 907023/335, 907023/337: vapor-tight
 | 
        
            | EMC | as per EN 61 326-1:1997 + Annex 1:1998 + Annex 2:2001
 | 
        
            | Inputs/outputs | 
        
            | Operating voltage range | 10 – 35V DC, 24V AC - with optional supply module: 100 – 240V AC 50/60Hz
 | 
        
            | Current drawn (20°C, Ub = 24V DC) | - When used with RS232C: ≤25mA - Output 2x 0 – 1V / 0 – 5V / 0 – 10V: ≤25mA
 - Output 2x 0 – 20mA: ≤60mA
 - With display and background lighting: 20mA
 - During sensor cleaning: 110mA max.
 - With probe heating (907023/337): 120mA
 | 
        
            | Analog outputs (2 are standard, 3rd is optional) | - Current output: 0 – 20mA, 4 – 20mA - Voltage output: 0 – 1V, 0 – 5V, 0 – 10V
 | 
        
            | Accuracy of the analog outputs | At 20°C: ±0.05% of full scale | 
        
            | Temperature drift of the analog outputs
 | ±0.005% of full scale | 
        
            | External loads | - Burden for current outputs: <500Ω - Voltage output 0 – 1V: >2kΩ
 - Voltage output 0 – 5V / 0 – 10V: >10kΩ
 | 
        
            | Maximum core cross-section | 0.5mm2 | 
        
            | Serial interface | RS232C, RS485 (option) | 
        
            | Relay outputs (option) | 0.5A, 250V AC | 
        
            | Digital display | LCD with background lighting, graphical trend display of all
 variables
 | 
        
            | Menu languages | English, German, French, Spanish, Japanese, Swedish,
 Finnish
 | 
        
            | General data | 
        
            | Connection options | - Cable gland: M 20x1.5 for 8 –11mm dia. cable - Conduit fitting (option): M 20x1.5 / NPT 1/2"
 - Connector: M 12, 8-pole, type RKC8/9.M12
 - 5m connecting cable: M 12, 8-pole, type RKT8-282/5M
 | 
        
            | Probe cable diameter | - 907023/333: 6.0mm - All other probes: 5.5mm
 Housing material: G-AlSi 10 Mg (DIN 1725)
 Enclosure protection: IP65
 Weight: 1 to 2 kg, depending on the version
 |