Features
For measuring relative air humidity and temperature
Measurement throughout the humidity range of 0 to 100 % RH
Intelligent interchangeable probes for simple replacement
For operating temperatures between -40 and +80 °C
Option of separate probes for humidity and temperature
2 m, 5 m, or 10 m adapter cable for probe extension
Robust metal housing, suitable for clean rooms
Integrated LCD display (optional)
With standardized current or voltage outputs
Specification:
Sensing element |
Type: HC105 capacitive (SMD version, condensation permitted),
largely maintenance free in normal, clean air |
Measuring/working range |
0 to 100% rH |
Medium |
air, unpressurized, not corrosive |
Accuracy (incl. hysteresis, non-linearity and repeat accuracy) |
±(1.5 + 0.5% x measured value) % rH; (at <90% rH; -15 to +40°C)
2.5% rH; (at >90% rH; -15 to +40°C)
±(1.7 + 1.5% x measured value) % rH; (at -40 to +80°C)
The tolerance data includes the uncertainty of the factory calibration with an expansion factor k = 2 (double the standard deviation). The tolerance is calculated to EA-4/02, taking GUM (Guide to the Expression of Uncertainty in Measurement) into consideration. |
Temperature dependence of the electronics |
±0.006% rH/°C |
Response time rH (with stainless steel mesh filter) |
typ. <15s (at 20°C/t0.9) |
Temperature
Sensing element |
Pt1000 thin film temperature sensor
tolerance class A to DIN EN 60 751 |
Measuring range |
-40 to +60°C, measurement probes directly on the hygrothermal transducer
-40 to +80°C, remote measurement probes, by means of the adapter cable |
Measuring accuracy |
|
Temperature dependence of the electronics |
±0,007°C/°C |
Response time T (with stainless steel mesh filter) |
typ. <3mins (t0.63), with combined measurement probe (rH+T)
typ. <6mins (t0.63), for separate T measurement probe |
Analog outputs
0 to 100% rH/xx to yy°C
(for T scaling, see order details) |
0 to 1V (-0.5mA < IL <0.5mA)
0 to 5V/0 to 10V (-1mA < IL <1mA)
4 to 20mA (two-wire) (RL <500ohms) |
Temperature sensitivity of the analog outputs |
max. 0,2 mV/°C or 1 µA/°C |
Electrical data
Supply for
0 to 1V
0 to 5V
0 to 10V
4 to 20mA |
10 to 35V DC or 9 - 29V AC
12 to 35V DC or 15 - 29V AC
15 to 35V DC or 15 - 29V AC
10 to 35V DC |
Burden (I output) |
RL < Uv 10V/0.02A[Ω] |
General information
Housing |
Al Si 9 Cu 3 |
Probes |
stainless steel 1.4305 (reference probes made of PC plastic) |
Dimensions |
Housing: 163(135)mm x 90mm x 50mm (W x H x D)
(rH/T) probe: 13mm x 91mm (D x L)
(T) probe (separate): 12(6)mm x 93mm (D x L) |
Cable gland |
M 16 x1.5 (Lumberg connector option (RSF 50/11)) |
Terminals |
Screw terminals for cable cross-sections up to 2.5mm2 |
Housing protection class |
IP65 (IP10 for rear cable entry, IP40 for plain wall mounting) |
Ambient temperatures |
Measurement probe: -40 to +60°C (+80°C with adapter cable)
Electronics: -40 to +60°C
Storage temperature: -40 to +60°C |
Sensor protection |
PTFE filter, pore size: 50µm
High chemical resistance, response time t0.1/0.9: typ. 14s
Stainless steel mesh filter (standard),
for average pollution, high mechanical strength,
suitable for high humidity applications, response time t0.1/0.9: typ. 7s |
Weight |
approx. 800g |
|