                | Parameter  | 
                Value  | 
             
            
                | Supply voltage 3-phaseAC (50 Hz), | 
                380 ± 38 | 
             
            
                | Consumption power, kW∙A, max  | 
                 250  | 
             
            
                | Continuous operation at maximum capacity, min, max  | 
                20 
                 | 
             
            
                Break after continuous use, min, min  
                 | 
                40 | 
             
            
                | Output power, kV∙A | 
                1400 | 
             
            
                | Capacitance range of objectsTest, uF | 
                0,01- 1,5 | 
             
            
                | Q-factor, min | 
                20 | 
             
            
                | Maximum operating voltage AC test mode of the stator winding, kV | 
                35 | 
             
            
                | Maximum operating voltage AC test mode of the busway, kV | 
                70 | 
             
            
                | Maximum operating voltage is rectified current in the test mode leakage currents, kV | 
                100 | 
             
            
                Reduced error measuring current and voltage, max,%  
                 | 
                3 | 
             
            
                Treshold current protection high-voltage side, A  
                 | 
                32 | 
             
            
                Treshold current protection low-voltage side, no more, A  
                 | 
                350 | 
             
            
                | Dimensions L × W × H, mm  | 
                4400 × 2000 × 2100  
                 | 
             
            
                Warranty life, h  
                 | 
                1200 | 
             
            
                Weight, kg, no more  
                 | 
                13,000 | 
             
        
     
     
     
     
    - Operating Conditions
 
    
    
    The device is designed for an indoors operation under the following conditions: 
    
        
            
                | Condition | 
                Value | 
             
            
                | Air temperature, °С | 
                from +10 to +35 
                 | 
             
            
                Relative humidity, %, up to 
                 | 
                80 at +25 °С | 
             
            
                Atmospheric pressure, kPa (mm hg) 
                 | 
                84,0 – 106,7 (630 – 800) | 
             
        
     
     
     
 
  
                             |